System Selector 

The System Selector below will help you choose the correct system. Simply tick the boxes that apply to your situation and click "Search Systems".
You can also use this page to create your own Firestopping Specification. To see how go to Specification Instructions
If you want to restrict your search to a particular product, click your choice from the "Product" dropdown menu. 
If you know the identification number (FCxxx) of the system(s) you want then simply type them into the "System ID" box (separate by commas for multiple numbers) and click "Search Systems".
For an Excel spreadsheet version of all systems, click here for a list of systems.
Important Note: Systems tested in plasterboard may also be used in concrete (AS 1530.4 Section 10.12.2). Therefore all the systems shown below with diagrams in plasterboard may be used in concrete.

Wall
Floor
Ceiling
Plasterboard
Concrete
CLT
Korok/Speedpanel
Plastic Pipe
PEX Pipe
AluPEX Pipe
Metal Pipe
Copper/Brass Pipe
Cables
Cable Trays
Conduits
Pair Coils
Elect Dist Box
Joints and Gaps
Tilt Slab
Steel
Combos
Ducts
Smoke Seal
Blanks
Hatches
Collars

Product :
Required Fire Rating :
System ID(s) :
Search Systems    

3M Duct Wrap 615+ Single Layer, Internal or External Fire

System ID FC232

Duct (up to 1250 x 1000mm) in open spaces or passing through any non fire-rated construction. Internal and external fire protection. Single layer 3M Duct Wrap 615+ for up to -/180/180 fire protection.

3M Duct Wrap 615+, Plasterboard Wall, Internal or External Fire

System ID FC230

Duct (up to 1200 x 1200mm) through a fire-rated plasterboard wall. Protection from internal or external fire. 3M Duct Wrap 615+ single layer for duct and double layer adjacent to penetration (third layer of 150mm required for 120mins). Plasterboard or Glasroc collar with fillet of 3M Fire Barrier CP25WB sealant. FRR -/120/120

3M Duct Wrap 615+, Concrete Wall, Internal or External Fire

System ID FC498

Duct (up to 1200 x 1200mm) through a fire-rated concrete, masonry, AAC or Speedpanel wall. Protection from internal or external fire. 3M Duct Wrap 615+ single layer for duct and double layer adjacent to penetration (third layer of 150mm required for 120mins). Plasterboard or Glasroc collar with fillet of 3M Fire Barrier CP25WB sealant. FRR -/120/120

3M Duct Wrap 615+, Any Wall, No Collar, Internal Fire

System ID FC499

Duct (up to 3600 x 3600mm) through any fire-rated wall. Protection from internal fire. 3M Duct Wrap 615+ single layer for duct and three extra layers adjacent to penetration. No collar required. With fillet of 3M Fire Barrier CP25WB sealant. FRR 60/60/60

3M Duct Wrap 615+, Concrete Floor, External Fire

System ID FC231

Duct (up to 1250 x 1000mm) through a fire-rated concrete floor. Protection from external fire (up to 240mins). 3M Duct Wrap 615+ single layer around duct with double layer at penetration. Plasterboard collar finished with 3M Fire Barrier CP25WB+ sealant.

3M Duct Wrap 615+, Concrete Floor, Internal Fire

System ID FC501

Duct (up to 3600 x 3600mm) through a fire-rated concrete floor. Protection from internal fire (up to 120mins). 3M Duct Wrap 615+ single layer around duct with two extra layers at penetration. Plasterboard collar on top side only finished with 3M Fire Barrier CP25WB+ sealant.

3M Duct Wrap 615+ VentureClad

System ID FC560

Protection of ducts wrapped with 3m Duct Wrap 615+ when exposed to weathering or other external conditions. Apply 3M Duct Wrap 615+ as per an approved system and wrap the entire duct with 3M VentureClad Wrap according to the attached instructions.