System Selector 

The System Selector below will help you choose the correct system. Simply tick the boxes that apply to your situation and click "Search Systems".
You can also use this page to create your own Firestopping Specification. To see how go to Specification Instructions
If you want to restrict your search to a particular product, click your choice from the "Product" dropdown menu. 
If you know the identification number (FCxxx) of the system(s) you want then simply type them into the "System ID" box (separate by commas for multiple numbers) and click "Search Systems".
For an Excel spreadsheet version of all systems, click here for a list of systems.
Important Note: Systems tested in plasterboard may also be used in concrete (AS 1530.4 Section 10.12.2). Therefore all the systems shown below with diagrams in plasterboard may be used in concrete.

Wall
Floor
Ceiling
Plasterboard
Concrete
CLT
Korok/Speedpanel
Plastic Pipe
PEX Pipe
AluPEX Pipe
Metal Pipe
Copper/Brass Pipe
Cables
Cable Trays
Conduits
Pair Coils
Elect Dist Box
Joints and Gaps
Tilt Slab
Steel
Combos
Ducts
Smoke Seal
Blanks
Hatches
Collars

Product :
Required Fire Rating :
System ID(s) :
Search Systems    

3M CP 25WB+ Concrete Floor Cables

System ID FC216

Cables (multiple, with or without cable tray) through a concrete floor (120mm min). 3M CP 25WB+ sealant 40mm deep at top of floor only, backed by 80mm mineral wool. Annular space 25-60mm. Thermal up to 120 available using 3M E-5A-4 Endothermic Mat. Max FRR -/180/120

3M CP 25WB+ P'board Wall Cables

System ID FC217

Cables (D1 and D2 cables as per AS1530.4, including cable trays) through a plasterboard or concrete wall. 3M CP 25WB+ sealant to 20mm to both sides of the wall, with 75mm mineral wool backing. Thermal of 120 available using 3M E-5A-4 Endothermic Mat. Max FRR -/120/120

3M CP 25WB+ P'board Wall Metal Pipes

System ID FC350

Steel, copper or ferrous pipes (uninsulated) through a plasterboard wall. 3M CP 25WB+ sealant to 25mm to both sides of wall with 100mm mineral wool backing. Thermal of 120 available using 3M E-5A-4 Endothermic Mat.

3M CP 25WB+ Concrete Wall Metal Pipes

System ID FC293

Steel, copper or ferrous pipes through a concrete wall. 3M CP 25WB+ sealant to 25mm to both sides of wall with 100mm mineral wool backing. Thermal of 120 available using 3M E-5A-4 Endothermic Mat.

3M CP 25WB+ P'board or Concrete Wall Conduit

System ID FC535

Conduit up to 26mm diameter through a plasterboard or concrete wall. 3M CP 25WB+ sealant to 26mm to both sides of wall. Designed for fibre optic conduits. Wall cavity insulation optional. Annular space up to 10mm.

3M CS-195 23695 Floor

System ID FC224

Cables D1and D2, cable trays, metallic pipes in any combination or blanks through a concrete floor min 100mm slab depth. Max aperture 425x300mm. 3M Composite Sheet CS-195, 1 or 2 layers. Wrap strips, putty and sealant as required - see detailed instructions. Insulation up to 120 by wrapping with E-5A-4 Mat

3M CS-195 23695 Wall

System ID FC225

Cables D1 and D2, cable trays, blanks or metallic pipes through a plasterboard or concrete wall in various combinations. Wall min 120mm thick. Aperture max 800x600mm. 3M Composite Sheet CS-195 to each side of wall. Wraps and sealant as required. Insulation increased to 120 by wrapping with E-5A-4 Mat.

3M Tuck-In Wrap Strip Concrete Wall PVC Pipe

System ID FC87

Plastic pipe (PVC-U up to 110mm) through a 100mm concrete, AAC or masonry block wall. Single or double layer 3M Tuck-in Wrap Strip to each side with IC 15WB+ or CP 25WB+ sealant. Max FRR -/120/120

3M Tuck-In Wrap Strip Concrete Wall PVC Pipe One-sided

System ID FC361

Plastic pipe (PVC-U up to 110mm) through a 100mm concrete, AAC or masonry wall. Single or double 3M Tuck-In Wrap Strips with 3M IC 15WB or 3M CP 25WB sealant 30mm deep to one side of the wall. 

3M Tuck-In Wrap Strip Plasterboard Wall PVC Pipe

System ID FC288

Plastic pipe (PVC-U up to 110mm) through a plasterboard wall. Single or double layer 3M Tuck-In Wrap Strips with 3M IC 15WB+ or 3M CP 25WB+ sealant to both sides of the wall. No wall insulation required. Max FRR -/120/120