System Selector 

The System Selector below will help you choose the correct system. Simply tick the boxes that apply to your situation and click "Search Systems".
You can also use this page to create your own Firestopping Specification. To see how go to Specification Instructions
If you want to restrict your search to a particular product, click your choice from the "Product" dropdown menu. 
If you know the identification number (FCxxx) of the system(s) you want then simply type them into the "System ID" box (separate by commas for multiple numbers) and click "Search Systems".
For an Excel spreadsheet version of all systems, click here for a list of systems.
Important Note: Systems tested in plasterboard may also be used in concrete (AS 1530.4 Section 10.12.2). Therefore all the systems shown below with diagrams in plasterboard may be used in concrete.

Wall
Floor
Ceiling
Plasterboard
Concrete
CLT
Korok/Speedpanel
Plastic Pipe
PEX Pipe
AluPEX Pipe
Metal Pipe
Copper/Brass Pipe
Cables
Cable Trays
Conduits
Pair Coils
Elect Dist Box
Joints and Gaps
Tilt Slab
Steel
Combos
Ducts
Smoke Seal
Blanks
Hatches
Collars

Product :
Required Fire Rating :
System ID(s) :
Search Systems    

Protecta FR Collar Concrete Floor Blank

System ID FC443

Blank seal up to 160mm diameter in a concrete floor. Minimum floor thickness 100mm. Protecta collar fixed to underside of floor, with Protecta FR Acrylic sealant. Max FRR -/240/120

Protecta FR Collar Concrete Floor Plastic Pipe

System ID FC146

Combustible pipe up to 400mm (PVC, PP, PE, PEX, HDPE, PP-R, Acoustic, Aquatherm, etc) through a 100mm concrete floor. Protecta collar fixed to underside of floor, with Protecta FR Acrylic sealant. Oversize collars permitted. Zero smoke at 200Pa. Max FRR -/240/240

Protecta FR Collar Concrete Floor Plastic Pipe Top-fix

System ID FC444

Combustible pipe 32-160mm (PVC, PP, PEX, PE, PP-R, etc) through a 100mm concrete floor. Protecta collar fixed to top side of floor, with Protecta FR Acrylic sealant to top of collar only. No oversize collars permitted. Max FRR -/240/240

Protecta FR Collar Composite Floor Plastic Pipe

System ID FC438

Plastic pipes up to 160mm (PVC, PE, HDPE, PEX, PP, PP-R, etc) through a composite floor. Protecta FR Collar to top side only. No minimum topping required. Finish with bead of Protecta FR Acrylic sealant to top of collar. Max FRR -/240/240

Protecta FR Collar Concrete Floor Conduits

System ID FC440

Conduits (rigid or flexible up to 32mm) of PVC, PE, PEX single or in bundles up to 160mm diam through a 100mm concrete floor. Protecta collar fixed to underside of floor, with Protecta FR Acrylic sealant. Zero smoke leakage up to 200Pa. Max FRR -/90/90

Protecta FR Collar Concrete Floor Cables

System ID FC442

Cable bundles up to 160mm (electrical, data or fibre optic) through a 100mm concrete floor. Protecta collar to underside of floor with Protecta FR Acrylic sealant. Zero smoke leakage up to 200Pa with 10mm FR Acrylic. Max FRR -/180/180

Protecta FR Collar Concrete Floor Metal/Plastic Pipe Combustible/Non-combustible Insulation

System ID FC441

Insulated pipes (Copper or steel up to 54mm diam, Alupex to 75mm, PP/PE to 160mm) with combustible or non-combustible insulation through a 100mm concrete or AAC floor. Protecta collar to underside of floor with Protecta FR Acrylic sealant. Zero smoke leakage up to 200Pa with 10mm FR Acrylic. Max FRR -/180/180

Protecta FR Collar Timber Infill Approval

System ID FC473

Protecta FR Collars have been tested in timber floors, so may be used in situations where a timber infill has been left in place under a concrete slab floor. All existing approvals for FR Collars up to 160mm can be used with fixings passing through the timber infill and penetrating 40mm into the concrete slab. See the Timber Infill Approval document for details. Zero smoke leakage up to 200Pa. Max FRR -/120/120

Protecta FR Collar Timber Floor Plastic Pipe

System ID FC147

Combustible pipe up to 400mm (PVC, PP, PE, PEX, HDPE, PP-R, Acoustic, Aquatherm, etc) through a 150mm solid timber or CLT floor. Protecta collar fixed to underside of floor, with Protecta FR Acrylic sealant top and bottom. Oversize collars permitted. Zero smoke leakage up to 200Pa. Max FRR -/240/240

Protecta FR Collar Timber Floor Conduits

System ID FC439

Conduits (rigid or flexible up to 32mm) of PVC, PE, PEX single or in bundles up to 160mm diam through a 150mm solid timber or CLT floor. Protecta collar fixed to underside of floor, with Protecta FR Acrylic sealant top and bottom. Zero smoke leakage up to 200Pa. Max FRR -/90/90

Protecta FR Collar Timber Floor Cables

System ID FC595

Cable bundles up to 160mm (electrical, data or fibre optic) through a 150mm solid timber or CLT floor. Protecta collar to underside of floor with Protecta FR Acrylic sealant. Zero smoke leakage up to 200Pa. Max FRR -/180/180

Protecta FR Collar Timber Floor Metal/Plastic Pipe Combustible/Non-combustible Insulation

System ID FC596

Insulated pipes (Copper or steel up to 54mm diam, Alupex to 75mm, PP/PE to 160mm) with combustible or non-combustible insulation through a 150mm solid timber or CLT floor. Protecta collar to underside of floor with Protecta FR Acrylic sealant. Zero smoke leakage up to 200Pa. Max FRR -/180/180

Protecta FR Collar Pbd Wall Blank Seal

System ID FC436

Blank seal up to 160mm in a plasterboard wall. Protecta collar both sides, with stone or mineral wool plug. Min wall 100mm. Max FRR -/120/120

Protecta FR Collar Single Layer Standard Plasterboard Wall

System ID FC480

Combustible pipe 32-160mm (PVC, PE, PP) through a plasterboard wall with single layer Standard board 10mm or 13mm. Protecta collar both sides, with Protecta FR Acrylic sealant. Oversize collars permitted. Minimum wall thickness 51mm. Zero smoke leakage up to 200Pa. Max FRR -/60/30

Protecta FR Collar Single Layer Plasterboard Wall

System ID FC541

Combustible pipe 32-160mm (PVC, PE, HDPE, PEX, PP, PP-R, etc) through a single layer plasterboard wall. Protecta collar both sides, with Protecta FR Acrylic sealant. Oversize collars permitted. Min wall 75mm. Zero smoke leakage up to 200Pa with 10mm FR Acrylic. Max FRR -/60/60

Protecta FR Collar Plasterboard Wall Plastic Pipe

System ID FC144

Combustible pipe 32-400mm (PVC-U, PVC-C, PE, HDPE, PEX, PP, PP-R, PP-MV etc) through a plasterboard wall. Protecta collar both sides, with Protecta FR Acrylic sealant. Oversize collars permitted. Min wall thickness 100mm. Zero smoke leakage up to 200Pa with 10mm FR Acrylic. Max FRR -/120/120

Protecta FR Collar Pbd Wall Composite Pipe

System ID FC432

Low-noise waste pipes (mineral reinforced PP) and Aquatherm domestic water pipes (PP-R, PP-RP, PP-RCT) 32-160mm through a plasterboard wall. Protecta collar both sides, with Protecta FR Acrylic sealant. Oversize collars permitted. Min wall 100mm. Zero smoke leakage up to 200Pa with 10mm FR Acrylic. Max FRR -/120/120

Protecta FR Collar Pbd Wall Plastic Pipe Bundles

System ID FC598

Plastic pipes up to 40mm of any type (PVC-C, PVC-U, PE, HDPE, PEX, PP, PP-R, PP-MV, PP-H) in mixed bundles up to 160mm through a 100mm plasterboard wall. Protecta collar both sides, with Protecta FR Acrylic sealant. Zero smoke leakage up to 200Pa with 10mm FR Acrylic. Max FRR -/90/90

Protecta FR Collar Pbd Wall Cables

System ID FC434

Cables, single or bundled, (electrical with copper or aluminium conductors, fibre optic or data) up to 160mm through a plasterboard wall. Protecta collar both sides, with Protecta FR Acrylic sealant. Min wall 100mm. Zero smoke leakage up to 200Pa with 10mm FR Acrylic. Max FRR -/120/60

Protecta FR Collar Pbd Wall Conduits

System ID FC597

Conduits up to 40mm of any rigid or flexible plastic, single or bundled, with or without cables up to 21mm (electrical with copper or aluminium conductors, fibre optic or data) in mixed bundles up to 160mm through a 100mm plasterboard wall. Protecta collar both sides, with Protecta FR Acrylic sealant. Zero smoke leakage up to 200Pa with 10mm FR Acrylic. Max FRR -/90/90

Protecta FR Collar Pbd Wall Insulated Plastic Pipe

System ID FC599

PE or PP plastic pipes up to 160mm with combustible or non-combustible insulation through a plasterboard wall. Protecta collar both sides, with Protecta FR Acrylic sealant. Min wall 100mm. Zero smoke leakage up to 200Pa with 10mm FR Acrylic. Max FRR -/120/120

Protecta FR Collar Pbd Wall Insulated Metal Pipe

System ID FC437

Steel or Copper pipes up to 54mm or Alupex pipes up to 75mm with combustible or non-combustible insulation through a plasterboard wall. Protecta collar both sides, with Protecta FR Acrylic sealant. Min wall 100mm. Zero smoke leakage up to 200Pa with 10mm FR Acrylic. Max FRR -/120/90

Protecta FR Collar Pbd Wall Bare Metal Pipe

System ID FC435

Bare copper or steel pipes up to 54mm through a plasterboard wall. Protecta collar both sides, with Protecta FR Acrylic sealant. Min wall 100mm. Zero smoke leakage up to 200Pa with 10mm FR Acrylic. Max FRR -/120/90

Protecta FR Collar Oversize Approval

System ID FC433

Protecta FR Collars have been tested oversize, so they can be used in situations where a pipe is not square to the wall or floor, or where the aperture is over-size. Oversize collars can be used in walls or floors, concrete, timber or plasterboard and for pipes, cables or conduits. Collars up to 160mm can be used with any size pipe at angles up to 45degrees off-centre. See pages 9 and 52 of the Assessment for Oversize Approval details. Max FRR -/120/120

Protecta FR Collar Timber Wall Plastic Pipe

System ID FC602

Combustible pipe 32-400mm (PVC-U, PVC-C, PE, HDPE, PEX, PP, PP-R, PP-MV etc) through a 100mm solid timber or CLT wall. Protecta collar both sides, with Protecta FR Acrylic sealant. Oversize collars permitted. Min wall thickness 100mm. Zero smoke leakage up to 200Pa. Max FRR -/120/120

Protecta FR Collar Timber Wall Composite Pipe

System ID FC603

Low-noise waste pipes (mineral reinforced PP) and Aquatherm domestic water pipes (PP-R, PP-RP, PP-RCT) 32-160mm through a 100mm solid timber or CLT wall. Protecta collar both sides, with Protecta FR Acrylic sealant. Oversize collars permitted. Zero smoke leakage up to 200Pa. Max FRR -/120/120

Protecta FR Collar Timber Wall Plastic Pipe Bundles

System ID FC604

Plastic pipes up to 40mm of any type (PVC-C, PVC-U, PE, HDPE, PEX, PP, PP-R, PP-MV, PP-H) in mixed bundles up to 160mm through a 100mm solid timber or CLT wall. Protecta collar both sides, with Protecta FR Acrylic sealant. Zero smoke leakage up to 200Pa. Max FRR -/90/90

Protecta FR Collar Timber Wall Cables

System ID FC605

Cables, single or bundled, (electrical with copper or aluminium conductors, fibre optic or data) up to 160mm through a 100mm solid timber or CLT wall. Protecta collar both sides, with Protecta FR Acrylic sealant. Min wall 100mm. Zero smoke leakage up to 200Pa. Max FRR -/120/60

Protecta FR Collar Timber Wall Conduits

System ID FC606

Conduits up to 40mm of any rigid or flexible plastic, single or bundled, with or without cables up to 21mm (electrical with copper or aluminium conductors, fibre optic or data) in mixed bundles up to 160mm through a 100mm solid timber or CLT wall. Protecta collar both sides, with Protecta FR Acrylic sealant. Zero smoke leakage up to 200Pa. Max FRR -/90/90

Protecta FR Collar Timber Wall Insulated Plastic Pipe

System ID FC607

PE or PP plastic pipes up to 160mm with combustible or non-combustible insulation through a 100mm solid timber or CLT wall. Protecta collar both sides, with Protecta FR Acrylic sealant. Zero smoke leakage up to 200Pa. Max FRR -/120/120

Protecta FR Collar Timber Wall Insulated Metal Pipe

System ID FC608

Steel or Copper pipes up to 54mm or Alupex pipes up to 75mm with combustible or non-combustible insulation through a 100mm solid timber or CLT wall. Protecta collar both sides, with Protecta FR Acrylic sealant. Zero smoke leakage up to 200Pa. Max FRR -/120/90

Protecta FR Collar Timber Wall Bare Metal Pipe

System ID FC609

Bare copper or steel pipes up to 54mm through a 100mm solid timber or CLT wall. Protecta collar both sides, with Protecta FR Acrylic sealant. Zero smoke leakage up to 200Pa. Max FRR -/120/90

Protecta FR Collar Concrete Wall Plastic Pipe Single-sided

System ID FC550

Combustible pipe 32-160mm (PVC, PE, PE-HD, PEX, PP, PP-R, etc) through a concrete wall. Single Protecta collar to either side, with Protecta FR Acrylic sealant. Oversize collars permitted. Min wall thickness 75mm. Zero smoke leakage up to 200Pa with 10mm FR Acrylic. Max FRR -/240/180

Protecta FR Collar Concrete Wall Plastic Pipe

System ID FC145

Combustible pipe 32-400mm (PVC, PE, PE-HD, PEX, PP, PP-R, etc) through a concrete wall from 100mm. Protecta collar to both sides, with Protecta FR Acrylic sealant. Oversize collars permitted. Zero smoke leakage up to 200Pa with 10mm FR Acrylic. Max FRR -/240/240

Protecta FR Collar Concrete Wall Composite Pipe

System ID FC610

Low-noise waste pipes (mineral reinforced PP) and Aquatherm domestic water pipes (PP-R, PP-RP, PP-RCT) 32-160mm through a 100mm concrete, AAC or masonry wall. Protecta collar both sides, with Protecta FR Acrylic sealant. Oversize collars permitted. Zero smoke leakage up to 200Pa. Max FRR -/120/120

Protecta FR Collar Concrete Wall Plastic Pipe Bundles

System ID FC611

Plastic pipes up to 40mm of any type (PVC-C, PVC-U, PE, HDPE, PEX, PP, PP-R, PP-MV, PP-H) in mixed bundles up to 160mm through a 100mm concrete, AAC or masonry wall. Protecta collar both sides, with Protecta FR Acrylic sealant. Zero smoke leakage up to 200Pa. Max FRR -/90/90

Protecta FR Collar Concrete Wall Cables

System ID FC612

Cables, single or bundled, (electrical with copper or aluminium conductors, fibre optic or data) up to 160mm through a 100mm concrete, AAC or masonry wall. Protecta collar both sides, with Protecta FR Acrylic sealant. Zero smoke leakage up to 200Pa. Max FRR -/120/60

Protecta FR Collar Concrete Wall Conduits

System ID FC613

Conduits up to 40mm of any rigid or flexible plastic, single or bundled, with or without cables up to 21mm (electrical with copper or aluminium conductors, fibre optic or data) in mixed bundles up to 160mm through a 100mm concrete, AAC or masonry wall. Protecta collar both sides, with Protecta FR Acrylic sealant. Zero smoke leakage up to 200Pa. Max FRR -/90/90

Protecta FR Collar Concrete Wall Insulated Plastic Pipe

System ID FC614

PE or PP plastic pipes up to 160mm with combustible or non-combustible insulation through a 100mm concrete, AAC or masonry wall. Protecta collar both sides, with Protecta FR Acrylic sealant. Zero smoke leakage up to 200Pa. Max FRR -/120/120

Protecta FR Collar Concrete Wall Insulated Metal Pipe

System ID FC615

Steel or Copper pipes up to 54mm or Alupex pipes up to 75mm with combustible or non-combustible insulation through a 100mm concrete, AAC or masonry wall. Protecta collar both sides, with Protecta FR Acrylic sealant. Zero smoke leakage up to 200Pa. Max FRR -/120/90

Protecta FR Collar Concrete Wall Bare Metal Pipe

System ID FC616

Bare copper or steel pipes up to 54mm through a 100mm concrete, AAC or masonry wall. Protecta collar both sides, with Protecta FR Acrylic sealant. Zero smoke leakage up to 200Pa. Max FRR -/120/90

Protecta FR Board Concrete Wall Metal Pipe Comb Ins

System ID FC276

Metallic pipes (Copper to 54mm, Alupex to 75mm) with continuous combustible or non-combustible insulation through a concrete, AAC or masonry wall. Single Protecta FR Board 60mm 2-S anywhere in the aperture (max 1200 x 600mm). Protecta FR Collar either side of FR Board. Collar may be oversize to 110mm. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/60/60

Protecta FR Board Concrete Wall Plastic Pipes Collar

System ID FC104

Plastic pipes (PVC, PE, PEX, HDPE, etc) through a concrete wall min 75mm thick, Single Protecta FR Board 60mm 2-S anywhere in the aperture (max 1200 x 600mm) with Protecta FR Collar each side of FR Board. Finish with Protecta FR Acrylic sealant. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/120/60

Protecta FR Board Plasterboard Wall Plastic Pipe Collar

System ID FC172

Plastic pipes (PVC, HDPE, PEX, PP, PP-R, etc  all to 160mm) through a plasterboard wall. Protecta FR Board 60mm 2-sided to either side of the wall or anywhere inbetween. Protecta FR Collar to both sides of wall. Finish with Protecta FR Acrylic sealant. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/120/60

Protecta FR Board Plasterboard Wall Metal Pipe Combustible or Non-combustible Insulation

System ID FC170

Metallic pipes with continuous combustible or non-combustible insulation (Copper to 54mm, Alupex to 75mm) through a plasterboard wall. Protecta FR Collar to both sides of the wall. Finish with Protecta FR Acrylic sealant. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/60/60