System Selector 

The System Selector below will help you choose the correct system. Simply tick the boxes that apply to your situation and click "Search Systems".
You can also use this page to create your own Firestopping Specification. To see how go to Specification Instructions
If you want to restrict your search to a particular product, click your choice from the "Product" dropdown menu. 
If you know the identification number (FCxxx) of the system(s) you want then simply type them into the "System ID" box (separate by commas for multiple numbers) and click "Search Systems".
For an Excel spreadsheet version of all systems, click here for a list of systems.
Important Note: Systems tested in plasterboard may also be used in concrete (AS 1530.4 Section 10.12.2). Therefore all the systems shown below with diagrams in plasterboard may be used in concrete.

Wall
Floor
Ceiling
Plasterboard
Concrete
CLT
Korok/Speedpanel
Plastic Pipe
PEX Pipe
AluPEX Pipe
Metal Pipe
Copper/Brass Pipe
Cables
Cable Trays
Conduits
Pair Coils
Elect Dist Box
Joints and Gaps
Tilt Slab
Steel
Combos
Ducts
Smoke Seal
Blanks
Hatches
Collars

Product :
Required Fire Rating :
System ID(s) :
Search Systems    

Protecta FR Putty Cord Pbd or Concrete Wall Single Cable

System ID FC312

Single cable up to 80mm (electrical with copper or aluminium conductor, fibre optic, data) through a plasterboard or concrete wall. Max FRR -/120/120. Approved in single layer systems with lower FRR. Does not require annular space. Blank seal up to 14mm diameter. Click here for Tested System Tech Drawing.

Protecta FR Putty Cord Plasterboard Wall Cable Bundle

System ID FC349

Cable bundles up to 50mm (electrical with copper or aluminium conductors, fibre optic, data) through a plasterboard wall. Max FRR -/120/120. Approved in single layer systems with lower FRR. Does not require annular space. Blank seal up to 15mm diameter. Click here for Tested System Tech Drawing.

Protecta FR Putty Cord Plasterboard Wall Bare Pipe

System ID FC352

Uninsulated pipes (steel, copper or alupex) through a plasterboard wall. Max FRR -/120/120. Approved in single layer systems with lower FRR. Does not require annular space. Click here for Tested System Tech Drawing.

Protecta FR Putty Cord Plasterboard Wall Pipe LI

System ID FC353

Metal pipes (steel, copper, local interrupted insulation) through a plasterboard wall. Max FRR -/120/120. Approved in single layer systems with lower FRR. Does not require annular space. Click here for Tested System Tech Drawing.

Protecta FR Putty Cord Plasterboard Wall Pipe CS

System ID FC354

Metal pipes (steel, copper, continuous insulation) through a plasterboard wall. Max FRR -/120/120. Approved in single layer systems with lower FRR. Does not require annular space. Click here for Tested System Tech Drawing.

Protecta FR Putty Cord Concrete Wall Cable Bundle

System ID FC403

Cable bundles up to 50mm (electrical with copper or aluminium conductors, fibre optic, data) through a concrete wall min 100mm. Max FRR -/120/120. Does not require annular space. Blank seal up to 15mm diameter. Click here for Tested System Tech Drawing

Protecta FR Putty Cord Concrete Wall Bare Pipe

System ID FC404

Uninsulated pipes (steel, copper or alupex) through a concrete wall, min 100mml. Max FRR -/120/120. Does not require any annular space. Click here for Tested System Tech Drawing

Protecta FR Putty Cord Concrete Wall Pipe LI

System ID FC405

Metal pipes (steel, copper, local interrupted insulation) through a concrete wall, min 100mm. Max FRR -/120/120. Does not require annular space. Click here for Tested System Tech Drawing

Protecta FR Putty Cord Concrete Wall Pipe CS

System ID FC406

Metal pipes (steel, copper, continuous insulation) through a concrete wall, min 100mm. Max FRR -/120/120. Does not require annular space. Click here for Tested System Tech Drawing

Protecta FR Putty Cord Concrete Floor Cable Bundle Top

System ID FC355

Cables, single or bundles up to 50mm (electrical with copper or aluminium conductors, fibre optic, data), through a concrete floor min 100mm. Protecta Putty Cord fillet to top side of floor only. Max FRR -/240/240. Does not require annular space. Blank seal up to 15mm diameter. Click here for Tested System Tech Drawing

Protecta FR Putty Cord Concrete Floor Cable Bundle Soffit

System ID FC356

Cables, single or bundles up to 75mm (electrical with copper or aluminium conductors, fibre optic, data), through a concrete floor min 100mm. Protecta Putty Cord fillet to soffit side of floor only. Max FRR -/120/60. Does not require annular space. Blank seal up to 15mm diameter. Click here for Tested System Tech Drawing

Protecta FR Putty Cord Concrete Floor Bare Pipe Top

System ID FC358

Pipes (uninsulated, steel to 22mm, copper to 10mm) through a concrete floor min 100mm. Protecta Putty Cord fillet to top side of floor only. Max FRR -/120/120. Does not require annular space. Click here for Tested System Tech Drawing

Protecta FR Putty Cord Concrete Floor Bare Pipe Soffit

System ID FC357

Pipes (uninsulated, steel to 30mm, copper to 12mm) through a concrete floor min 100mm. Protecta Putty Cord fillet to soffit side of floor only. Max FRR -/120/120. Does not require annular space. Click here for Tested System Tech Drawing

Protecta FR Putty Cord Concrete Floor LI Pipe

System ID FC359

Pipes (interrupted insulation, steel to 324mm, copper to 54mm) through a concrete floor min 100mm. Protecta Putty Cord fillet to top side of floor only. Max FRR -/240/240. Does not require annular space. Click here for Tested System Tech Drawing

Protecta FR Putty Cord Concrete Floor CS Pipe

System ID FC360

Pipes (continuous insulation, steel to 324mm, copper to 54mm) through a concrete floor min 100mm. Protecta Putty Cord fillet to top side of floor only. Max FRR -/240/240. Does not require annular space. Click here for Tested System Tech Drawing