3M Putty Concrete Floor Cables and Trays

Cables (power or communication, D1 & D2, cable trays) through a concrete floor 120mm min. 3M Mouldable Putty wrapped around penetrant for depth of floor then fill any aperture with 40mm putty top surface only backed with 80mm mineral wool. Increased thermal up to 120 available using 3M Duct Wrap 615+. Max FRR -/180/120

 

Products

Details

System ID #: 222
Max Fire Rating: 180
Max Thermal Rating: Up to 120 with 615 Duct Wrap
Size: Cables D1 & D2, with or without cable tray

System products available for purchase

Buy products

Build specifications

Add to specification

Associated Products & Downloads

Below are the downloads available. Please tick the ones you would like to receive and complete your details and select how you would like the files delivered to you. Alternatively you can click on the individual download name to view it now.

  Select All
  System diagram
  FC222 3M Putty Concrete Floor Cables or Cable Trays Tech Drawing
  AS1530 D1 and D2 Cables
  3M Fire Barrier Mouldable Putty AS1530.4 CSIRO RIR FCO3220

3M™ Fire Barrier Mouldable Putty
  3M Fire Barrier Mouldable Putty Data Sheet
  Mouldable Putty Safety Data Sheet
  3M FM Product Approval
  3M LEED Cert - Environmental Quality VOC