System Selector

The System Selector below will help you choose the correct system. Simply tick the boxes that apply to your situation. If you want to restrict your search to a single manufacturer, click your choice from the dropdown menu. If you know the identification number of the system you want, click here for a list of systems.
Important Note: Systems tested in plasterboard may also be used in concrete (AS 1530.4 Section 10.12.2). Therefore all the systems shown below with diagrams in plasterboard may be used in concrete. Many systems (tested to EN1366) also are available for timber floors and walls.

Showing systems that use Trafalgar FyreFLEX Sealant only.

Plasterboard
Concrete
Wall
Floor
Ceiling
Plastic Pipe
PEX Pipe
Metal Pipe
Copper Pipe
Cables
Cable Trays
Conduits
Elect Dist Box
Joints and Gaps
Combos
Ducts
Smoke Seal
Blanks

Manufacturer :
Required Fire Rating :
System ID :

View

Trafalgar FyreFlex Plasterboard Ceiling Cable

System ID FC431

Cable penetration through a plasterboard ceiling. Max annular space of 20mm. Fill gap with FyreFlex Sealant to the depth of the plasterboard. Fire rating 60minutes.