System Selector 

The System Selector below will help you choose the correct system. Simply tick the boxes that apply to your situation and click "Search Systems".
You can also use this page to create your own Firestopping Specification. To see how go to Specification Instructions
If you want to restrict your search to a particular product, click your choice from the "Product" dropdown menu. 
If you know the identification number (FCxxx) of the system(s) you want then simply type them into the "System ID" box (separate by commas for multiple numbers) and click "Search Systems".
For an Excel spreadsheet version of all systems, click here for a list of systems

Wall
Floor
Ceiling
Plasterboard
Concrete
CLT
Korok/Speedpanel
Plastic Pipe
PEX Pipe
AluPEX Pipe
Metal Pipe
Copper/Brass Pipe
Cables
Cable Trays
Conduits
Pair Coils
Elect Dist Box
Joints and Gaps
Tilt Slab
Steel
Combos
Ducts
Smoke Seal
Blanks
Hatches
Collars
Naked Wall

Product :
Required Fire Rating :
System ID(s) :
Search Systems    

FBL-100 C-Purlins through P'bd Wall

System ID FC228

C-Purlin (200mm to 400mm) through a 1 x 13mm plasterboard wall. Tech Coatings FBL-100 Intumescent Paint applied for 300mm on fire side only (or both sides for two-way application). May be used for any rolled steel profile 1.15mm to 3mm thick.  FRR -/60/60

FBL-100 Timber through 60min P'bd Wall

System ID FC290

Timber trusses (with or without exposed vertical web) or purlins through a 1 x 13mm plasterboard wall. Tech Coatings FBL-100 Intumescent Paint applied for 300mm on fire side only (or both sides for two-way application). May be used for any timber 90mm x 45mm or greater.  FRR -/60/60

FBL-100 Timber through 30min Standard P'bd Wall

System ID FC289

Timber trusses (with or without exposed vertical web) or purlins through a 1 x 13mm standard plasterboard wall. Tech Coatings FBL-100 Intumescent Paint applied for 300mm on fire side only (or both sides for two-way application). May be used for any timber 90mm x 45mm or greater.  FRR -/30/30