System Selector 

Use the Firestop Centre System Selector below to identify the most appropriate firestopping system for your project. Select the criteria that correspond to your firestopping requirements to view relevant options.

Additional features include:

  • The ability to create a custom Firestopping Specification — refer to the Specification Instructions Specification Instructions for guidance.
  • Filtering results by selecting a product from the Product dropdown menu.
  • Searching by system FC number by entering one or more FC numbers in the System ID box, separated by commas.
Substrate:   
Wall
Floor
Ceiling
Plasterboard
Concrete
CLT
Korok/Speedpanel
Hebel
Shaftwall

Penetrant:   
Metal Pipe
Copper/Brass Pipe
Cables
Cable Trays
Conduits
Pair Coils
Elect Dist Box
Joints and Gaps
Steel
Ducts
Blanks
Hatches
Naked Wall
Plastic Pipe
PEX Pipe
AluPEX Pipe

Product :
Required Fire Rating :
System ID(s) :
Search Systems    

FIRESTOP Duct Wrap-25 - Circular Duct Internal Fire - PB/Conc. Wall

System ID FC401

Service Penetration: Circular duct up to 300mm diameter
Fire Source: Internal fire
Substrate: 1 x 13mm Plasterboard on concrete wall, min. 90 thick
Max FRR: 120/120/60

FIRESTOP Duct Wrap-25 - Circular Duct Internal Fire One-Way System - PB/Conc. Wall

System ID FC542

Service Penetration: Circular duct up to 300mm diameter
Fire Source: Internal fire, one-way system
Substrate: 1 x 13mm Plasterboard on concrete wall, min. 90 thick
Max FRR: 120/120/60

FIRESTOP Duct Wrap-25 - Circular Duct Internal Fire - Composite/Conc. Floor

System ID FC224

Service Penetration: Circular duct up to 300mm diameter
Fire Source: Internal fire
Substrate: Composite (min. 60mm topping) or concrete flat slab floor, min. 120mm thick
Max FRR: 120/120/30