System Selector 

Use the Firestop Centre System Selector below to identify the most appropriate firestopping system for your project. Select the criteria that correspond to your firestopping requirements to view relevant options.

Additional features include:

  • The ability to create a custom Firestopping Specification — refer to the Specification Instructions Specification Instructions for guidance.
  • Filtering results by selecting a product from the Product dropdown menu.
  • Searching by system FC number by entering one or more FC numbers in the System ID box, separated by commas.
Substrate:   
Wall
Floor
Ceiling
Plasterboard
Concrete
CLT
Korok/Speedpanel
Hebel
Shaftwall

Penetrant:   
Metal Pipe
Copper/Brass Pipe
Cables
Cable Trays
Conduits
Pair Coils
Elect Dist Box
Joints and Gaps
Steel
Ducts
Blanks
Hatches
Naked Wall
Plastic Pipe
PEX Pipe
AluPEX Pipe

Product :
Required Fire Rating :
System ID(s) :
Search Systems    

CSD Rise Ultra Wrap PPM

System ID FC235

Plastic pipe (up to 100mm) through a concrete wall. CSD Rise Ultra Wrap fitted tightly around pipe to 1/8 of diam of pipe. CSD Nofirno Sealant 5mm each side of wall for smoke and water seal.

CSD Rise Ultra Wrap PPP

System ID FC236

Plastic pipe (up to 100mm) through a plasterboard wall. CSD Rise Ultra Wrap fitted tightly around pipe. CSD Nofirno Sealant 5mm each side of wall for smoke and water seal. Max aperture 400x450mm.