Protecta FR Acrylic Timber Floor Cables
Cables (all types of insulated electric cables with copper or aluminium core, fibre optic cables, communication cables) up to 50mm diam single or 100mm bundles through a solid timber or CLT floor min 150mm thick. Protecta FR Acrylic Sealant depth 25mm both sides. Max hole size 220mm diameter. Zero smoke leakage up to 200Pa. Max FRR -/120/120

Products
Details
						System ID #: 411
						Max Fire Rating: 120
						Max Thermal Rating: 120
						Size: Cables single to 50mm or bundles up to 100mm
					
Build specifications
Downloads