Protecta FR Boardx2 Concrete Wall Cables, Conduits

Cables (single or bundles) and conduits through a concrete or masonry wall min 75mm thick. Protecta FR Board 60mm or 50mm to both sides of wall. Finish with Protecta FR Acrylic sealant. Pattress fit option available. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/240/180

Products

Details

System ID #: 310
Max Fire Rating: 240
Max Thermal Rating: 180
Size: Cable Bundles up to 100mm, Conduits 16mm

Build specifications

Add to specification

Downloads

Below are the downloads available. Please tick the ones you would like to receive and complete your details and select how you would like the files delivered to you. Alternatively you can click on the individual download name to view it now.

  Select All
  System diagram
  FC310 Protecta FR Board Concrete Wall Cable Bundle 2 Tech Drawing
  Protecta FR Board AS1530.4 Assessment

Enter your email address
Send a copy to this email address
How do you want them sent to you?
   Email to me
   Download them now - you will need to provide your email address above

Need Help?