System Selector 

Use the Firestop Centre System Selector below to identify the most appropriate firestopping system for your project. Select the criteria that correspond to your firestopping requirements to view relevant options.

Additional features include:

  • The ability to create a custom Firestopping Specification — refer to the Specification Instructions Specification Instructions for guidance.
  • Filtering results by selecting a product from the Product dropdown menu.
  • Searching by system FC number by entering one or more FC numbers in the System ID box, separated by commas.
Substrate:   
Wall
Floor
Ceiling
Plasterboard
Concrete
CLT
Korok/Speedpanel
Hebel
Shaftwall

Penetrant:   
Metal Pipe
Copper/Brass Pipe
Cables
Cable Trays
Conduits
Pair Coils
Elect Dist Box
Joints and Gaps
Steel
Ducts
Blanks
Hatches
Naked Wall
Plastic Pipe
PEX Pipe
AluPEX Pipe

Product :
Required Fire Rating :
System ID(s) :
Search Systems    

Protecta EX Mortar Blank Backed - Concrete Wall

System ID FC264

Service Penetration: Blank aperture
Substrate: Concrete wall, min. 100mm thick
Max FRR: -/180/120

Protecta EX Mortar Cables & Cable Trays Backed - Concrete Wall

System ID FC194

Service Penetration: Cables (single or bundles) and conduits with or without cable tray
Substrate: Concrete wall, min. 150mm thick
Max FRR: -/180/90

Protecta EX Mortar Blank - Concrete Wall

System ID FC265

Service Penetration: Blank aperture
Substrate: Concrete wall, min. 150mm thick
Max FRR: -/240/240

Protecta EX Mortar Cable Trays - Concrete Wall

System ID FC343

Service Penetration: Cable tray
Substrate: Concrete Wall, min. 150mm thick
Max FRR:  -/240/240

Protecta EX Mortar Metal Pipe CS Backed - Concrete Wall

System ID FC195

Service Penetration: Steel pipe up to 219mm with continuous (CS) insulation
Substrate: Concrete wall, min. 150mm thick
Max FRR: -/120/90

Protecta EX Mortar Metal Pipe CI Backed - Concrete Wall

System ID FC196

Service Penetration: Steel, copper and Alupex pipe (up to 219mm) with interrupted (CI) insulation
Substrate: Concrete wall, min. 150mm thick
Max FRR: -/240/240

Protecta EX Mortar Bare Metal Pipe Backed - Concrete Wall

System ID FC345

Service Penetration: Bare steel, copper and Alupex pipe (up to 219mm) 
Substrate: Concrete wall, min. 150mm thick
Max FRR: -/240/-

Protecta EX Mortar Metal Pipe Interrupted Insulation - Concrete Wall

System ID FC199

Service Penetration: Steel pipe up to 219mm with interrupted (LI or CI) insulation
Substrate: Concrete wall, min. 100mm thick
Max FRR: -/240/240

Protecta EX Mortar Bare Metal Pipe - Concrete Wall

System ID FC346

Service Penetration: Bare steel, copper and Alupex pipe (up to 219mm) 
Substrate: Concrete wall, min. 100mm thick
Max FRR: -/240/180

Protecta EX Mortar Metal Pipe CombustibIe or Non-combustible Insulation - Concrete Wall

System ID FC344

Service Penetration: Steel (up to 165mm) with combustible or non-combustible insulation
Substrate: Concrete wall, min. 100mm thick
Max FRR: -/240/240

Protecta EX Mortar Blank Backed - Concrete Floor

System ID FC267

Service Penetration: Blank aperture
Substrate: Concrete floor, min. 100mm thick
Max FRR: -/180/180

Protecta EX Mortar Cables Backed - Concrete Floor

System ID FC201

Service Penetration: Cables (single or bundles) 
Substrate: Concrete floor, min. 100mm thick
Max FRR: -/180/180

Protecta EX Mortar Cable Trays Backed - Concrete Floor

System ID FC336

Service Penetration: Cable tray
Substrate: Concrete floor, min. 100mm thick
Max FRR:  -/180/180

Protecta EX Mortar Blank - Concrete Floor

System ID FC268

Service Penetration: Blank aperture
Substrate: Concrete floor, min. 100mm thick
Max FRR: -/240/240

Protecta EX Mortar Cables - Concrete Floor

System ID FC337

Service Penetration: Cables (single or bundles) 
Substrate: Concrete floor, min. 100mm thick
Max FRR: -/180/120

Protecta EX Mortar Conduits - Concrete Floor

System ID FC567

Service Penetration: Plastic conduit (PVC, PE & PP) up to 110mm
Substrate: Concrete floor, min. 100mm thick
Max FRR: -/120/120

Protecta EX Mortar Cable Trays - Concrete Floor

System ID FC203

Service Penetration: Cable tray
Substrate: Concrete floor, min. 100mm thick
Max FRR:  -/180/180

Protecta EX Mortar Metal Pipe CI Backed - Concrete Floor

System ID FC202

Service Penetration: Steel, copper and Alupex pipe (up to 219mm) with interrupted (CI) insulation
Substrate: Concrete floor, min. 100mm thick
Max FRR: -/240/240

Protecta EX Mortar Metal Pipe CS Backed - Concrete Floor

System ID FC338

Service Penetration: Steel, copper and Alupex pipe up to 324mm with continuous (CS) insulation
Substrate: Concrete floor, min. 100mm thick
Max FRR: -/240/240

Protecta EX Mortar Metal Pipe Bare Backed - Concrete Floor

System ID FC339

Service Penetration: Bare steel, copper and Alupex pipe (up to 324mm) 
Substrate: Concrete floor, min. 100mm thick
Max FRR: -/180/180

Protecta EX Mortar Metal Pipe Interrupted Insulation - Concrete Floor

System ID FC204

Service Penetration: Steel, copper and Alupex pipe (up to 219mm) with interrupted (CI) insulation
Substrate: Concrete floor, min. 100mm thick
Max FRR: -/240/240

Protecta EX Mortar Bare Metal Pipe - Concrete Floor

System ID FC340

Service Penetration: Bare steel, copper and Alupex pipe (up to 219mm) 
Substrate: Concrete floor, min. 100mm thick
Max FRR: -/240/180

Protecta EX Mortar Metal Pipe Combustible or Non-combustible Insulation - Concrete Floor

System ID FC205

Service Penetration: Steel, copper and Alupex pipe (up to 324mm) with combustible insulation
Substrate: Concrete floor, min. 100mm thick
Max FRR: -/240/240

Protecta EX Mortar Plastic Pipe - Concrete Floor

System ID FC206

Service Penetration: Plastic pipe up (PVC, PP, PE, PEX, Acoustic, etc) up to 400mm
Substrate: Concrete floor, min. 100mm thick
Max FRR: -/240/240

Protecta EX Mortar Insulated Plastic Pipes - Concrete Floor

System ID FC568

Service Penetration: Plastic pipe up to 160mm with combustible (Elastomeric or foam) or non-combustible insulation
Substrate: Concrete floor, min. 120mm thick
Max FRR: -/240/240

Protecta EX Mortar Plastic Pipe - Concrete Floor

System ID FC207

Service Penetration: Plastic pipe (single, PP 40mm, PE 40mm & 110mm). PE 110mm requires 1 layer of Protecta FR Pipe Wrap 50mm
Substrate: Concrete flat slab, min. 100mm thick
Max FRR: -/120/120
Test Config: C/C - Installed pipe end conditions must match those tested.
Report Page: 81

Protecta EX Mortar SHS Column - CLT Floor

System ID FC705

Service Penetration: 150mm SHS Column, perpendicular or inclined
Substrate: CLT (Red Stag) floor, min. 125mm thick
Max FRR: -/90/90

Protecta EX Mortar Multiple Plastic Pipe - Concrete Floor

System ID FC208

Service Penetration: PVC pipe (multiple) up to 40mm
Substrate: Concrete flat slab, min. 100mm thick
Max FRR: -/120/120
Test Config: U/C & C/C - Installed pipe end conditions must match those tested.
Report Pages: 82 & 83

Protecta EX Mortar Cables & Trays - PB Wall

System ID FC211

Service Penetration: Cables (single or bundles) and conduits with or without cable tray
Substrate: Concrete wall, min. 100mm thick
Max FRR: -/120/120

Protecta EX Mortar Metal Pipe Interrupted Ins - PB Wall

System ID FC212

Service Penetration: Metal and Alupex pipe up to 219mm with interrupted (LI or CI) insulation
Substrate: 2 x 13mm Plasterboard wall, min. 100mm thick
Max FRR: -/120/120

Protecta EX Mortar Bare Metal Pipe - PB Wall

System ID FC562

Service Penetration: Bare copper, steel and alupex pipes (up to 219mm)
Substrate: 2 x 13mm Plasterboard wall, min. 100mm thick
Max FRR: -/120/-

Protecta EX Mortar Metal Pipe CombustibIe Insulation - PB Wall

System ID FC163

Service Penetration: Copper, steel and Alupex pipe (up to 165mm) with combustible insulation
Substrate: 2 x 13mm Plasterboard wall, min. 100mm thick
Max FRR: -/120/120