Download technical drawings Clicking this download button will produce a .zip file of all Technical Drawings for the systems showing for this search. This may save time for specifiers and others preparing documents for compliance purposes.
System ID FC110
Linear joint seals for single-layer plasterboard walls. Between head of wall and soffit of concrete floor (up to 25mm gap) or between vertical end of wall and concrete wall (up to 15mm gap). Protecta FR Acrylic Sealant to depth 12.5mm. Zero smoke leakage up to 200Pa. Max FRR -/60/45
View +Spec
System ID FC506
Linear joint seals for plasterboard walls. Between head of wall and soffit of concrete floor (up to 25mm gap) or between vertical end of wall and concrete wall (up to 15mm gap). Protecta FR Acrylic Sealant to depth 12.5mm. Zero smoke leakage up to 200Pa. Max FRR -/90/90
System ID FC296
Linear joint seals for double-layer plasterboard walls. Between head of wall and soffit of concrete floor (up to 30mm gap) or vertical end of wall and concrete wall (up to 30mm gap). Protecta FR Acrylic Sealant depth 12.5mm backed by 12.5mm mineral wool or Protecta FR Acrylic Sealant to the full depth of 25mm. Zero smoke leakage up to 200Pa. Max FRR -/120/120
System ID FC507
Linear joint seals between vertical end of wall and concrete wall with no stud backing (up to 30mm gap). Protecta FR Acrylic Sealant depth 12.5mm backed by 20mm mineral wool. Zero smoke leakage up to 200Pa. Max FRR -/120/120
System ID FC508
Linear joint seals for plasterboard or concrete walls between head of wall and steel substrate above (up to 30mm gap). Protecta FR Acrylic Sealant depth 12.5mm backed by 12.5mm mineral wool or Protecta FR Acrylic Sealant to the full depth of 25mm. Zero smoke leakage up to 200Pa. Max FRR -/120/60 (seal only - thermal rating of system determined by rating of steel)
System ID FC510
Linear joint seals for plasterboard or concrete walls between end of wall and steel column or substrate (up to 30mm gap). Protecta FR Acrylic Sealant depth 12.5mm backed by 12.5mm mineral wool or Protecta FR Acrylic Sealant to the full depth of 25mm. Zero smoke leakage up to 200Pa. Max FRR -/120/60 (seal only - thermal rating of system determined by thermal rating of the steel)
System ID FC563
Linear joint seals for plasterboard or concrete walls between wall and steel framing (such as fire doors) (up to 30mm gap). Protecta FR Acrylic Sealant depth 12.5mm backed by 12.5mm mineral wool or Protecta FR Acrylic Sealant to the full depth of 25mm. Zero smoke leakage up to 200Pa. Max FRR -/120/60
System ID FC509
Linear joint seals for plasterboard or concrete walls between head of wall and plasterboard ceiling above (up to 30mm gap). Protecta FR Acrylic Sealant depth 12.5mm backed by 12.5mm mineral wool or Protecta FR Acrylic Sealant to the full depth of 25mm. Max FRR -/120/60
System ID FC470
Linear joint seals between plasterboard or concrete walls and timber walls or floors, including single-sided seals. Protecta FR Acrylic Sealant 12.5mm backed by 12.5mm mineral wool (or simply fill with 25mm Acrylic sealant). Joint width up to 30mm. Ideal for sealing to timber floors or beams. Zero smoke leakage up to 200Pa. Max FRR -/90/60
System ID FC472
Linear joint seals between steel substrates (beams, columns, etc) in plasterboard or concrete walls. Protecta FR Acrylic Sealant 12.5mm backed by 12.5mm mineral wool (or simply fill with 25mm Acrylic sealant). Joint width up to 30mm. Thermal rating dependent on rating of steel. Zero smoke leakage up to 200Pa. Max FRR -/120/30
System ID FC322
Joint seal between wall elements or between wall and soffit of floor. Protecta FR Acrylic sealant 15mm to each side with 20mm stone wool backing. Joint width up to 30mm. Zero smoke leakage up to 200Pa. Max FRR -/240/240
System ID FC112
Linear joint seal between 100mm concrete/AAC floor slabs or gap seal between slab and wall. Protecta FR Acrylic Sealant depth 25mm backed with mineral wool. Joint width up to 100mm. Zero smoke leakage up to 200Pa. Max FRR -/240/240
System ID FC111
Joint seal between wall elements or between wall and soffit of floor. Protecta FR Acrylic sealant to one side. Joint width up to 50mm. Zero smoke leakage up to 200Pa. Max FRR -/240/120
System ID FC323
Linear joint seal between 100mm concrete/AAC floor slabs or gap seal between slab and wall. Protecta FR Acrylic Sealant depth 15mm both sides with mineral wool backing. Joint width up to 100mm. Zero smoke leakage up to 200Pa. Max FRR -/240/240
System ID FC412
Linear gap seal between 100mm concrete/AAC floor slabs lined with steel or aluminium. Protecta FR Acrylic Sealant depth 25mm (top) or 15mm (both sides) backed with mineral wool. Joint width up to 30mm. Zero smoke leakage up to 200Pa. Max FRR -/240/120 (but note thermal rating will depend on the thermal rating of the steel or aluminium).
System ID FC259
Blank seal in concrete wall from 75mm. Protecta FR Acrylic 12.5mm to 25mm single and double-sided. Aperture up to 300 x 300mm. Zero smoke leakage up to 200Pa. Max FRR -/240/240
System ID FC113
Electrical cable (single, up to 21mm diam) through a concrete wall. Protecta FR Acrylic Sealant depth 25mm. Max 300x300mm. Annular space min 7mm. Fire from both directions. Zero smoke leakage up to 200Pa. Max FRR -/240/120
System ID FC114
Cables (single up to 80mm, bundles up to 100mm) through a 100mm concrete wall. Protecta FR Acrylic Sealant depth from 12.5mm. Max 300x300mm. Annular min 10mm. Separation between cables or bundles 10mm. Zero smoke leakage up to 200Pa. Max FRR -/240/240
System ID FC116
Metal or alupex pipe (single, insulated, interrupted) through a concrete wall (steel to 219mmm, copper to 54mm, alupex to 75mm). Protecta FR Acrylic 25mm any position. Fire from both directions. Zero smoke leakage up to 200Pa. Max FRR -/240/240
System ID FC278
Metallic pipe (single, insulated, continuous, steel up to 324mm) through a concrete wall. Protecta FR Acrylic 25mm any position with mineral wool backing. Fire from both directions. Max 300x300mm or 504mm diam. Annular min 10mm. Separation min 30mm between seals. Zero smoke leakage up to 200Pa. Max FRR -/180/180
System ID FC328
Metal or alupex pipe (single, uninsulated) through a concrete wall (steel to 219mm, copper to 54mm, alupex to 75mm). Protecta FR Acrylic 25mm any position. Fire from both directions. Zero smoke leakage up to 200Pa. Max FRR -/240/-
System ID FC117
Metal or Alupex pipe (insulated, interrupted) through a concrete wall (steel to 219mm, copper to 54mm, Alupex to 75mm). Protecta FR Acrylic 12.5-25mm both sides with stone wool backing. Zero smoke leakage up to 200Pa. Max FRR -/240/240
System ID FC279
Metallic pipes (single, insulated, continuous, steel up to 324mm, copper up to 54mm, Alupex up to 75mm) through a 100mm concrete wall. Protecta FR Acrylic 12.5-15mm to both sides of wall with stone wool backing. Max 300x300mm or 300mm diam. Annular min 10mm. Separation min 30mm between seals. Zero smoke leakage up to 200Pa. Max FRR -/240/240
System ID FC327
Metal or alupex pipe (uninsulated) through a concrete wall (steel to 219mm, copper to 54mm, Alupex to 75mm). Protecta FR Acrylic 12.5-15mm both sides with stone wool backing. Zero smoke leakage up to 200Pa. Max FRR -/240/120
System ID FC324
Metal pipes with continuous combustible (elastomeric) or non-combustible insulation (Steel up to 273mm, Copper to 54mm, Alupex to 75mm) through a 100mm concrete, AAC or masonry wall. Protecta FR Acrylic 25mm to both sides of wall. Max 300x300mm or 300mm diam. Annular min 10mm. Separation min 30mm between seals. Zero smoke leakage up to 200Pa. Max FRR -/120/120
System ID FC325
Plastic pipes (single, PVC-U, PVC-C, PE, PE-HD, PEX, PP, PP-R up to 32mm) through a concrete wall from 100mm. Protecta FR Acrylic 25mm to both sides of wall. Max 300x300mm or 300mm diam. Annular min 10mm. Separation min 30mm between seals. Zero smoke leakage up to 200Pa. Max FRR -/240/240
System ID FC467
Conduit, flexible or rigid, (PVC, PP or PE, up to 40mm) through a 100mm concrete wall, fully or partially filled with cables (electrical, data or fibre optic) up to 21mm diam. Protecta FR Acrylic 25mm to both sides of wall. Annular space min 10mm, max 30mm. Separation min 30mm between seals. Zero smoke leakage up to 200Pa. Max FRR -/120/120
System ID FC329
Blank seal in single-layer 13mm plasterboard wall. Protecta FR Acrylic 13mm each side of wall. Rating -/60/60 up to 150 x 150mm or equivalent. Backing may be any material to hold sealant in place. No cavity insulation required. Zero smoke leakage up to 200Pa. Max FRR -/60/60
System ID FC174
Cables up to 21mm diam (electrical, data or fibre optic) single or bundled up to 100mm through single-layer 13mm plasterboard wall. Protecta FR Acrylic Sealant depth 12.5mm both sides of wall. No backing. Zero smoke leakage up to 200Pa. Max FRR -/60/45
System ID FC469
Conduit (PVC, PE or PP) up to 32mm through a single-layer 13mm plasterboard wall, partially or completely filled with cables (electrical, data or fibre optic) up to 21mm diam. Protecta FR Acrylic Sealant depth 12.5mm both sides of wall. Annular space 10-30mm. No backing required. Zero smoke leakage up to 200Pa. Max FRR -/60/45
System ID FC418
Plastic pipe up to 32mm (PVC, PE, PE-HD, PP, PEX, PP-R, etc) through a single layer 13mm plasterboard wall, Protecta FR Acrylic Sealant depth 13mm both sides of wall. No backing required. Zero smoke leakage up to 200Pa. Max FRR -/30/30
System ID FC341
Cables up to 21mm (power, data or fibre optic) single or bundled through one side only of single-layer 13mm plasterboard wall. Protecta FR Acrylic Sealant to depth 12.5mm. No backing. Zero smoke leakage up to 200Pa. Max FRR -/60/45
System ID FC330
Metal Pipe (steel to 22m, bare) through single-layer 13mm plasterboard wall. Protecta FR Acrylic Sealant depth 12.5mm both sides of wall. No backing. Zero smoke leakage up to 200Pa. Max FRR -/60/30
System ID FC331
Steel pipe up to 324mm with continuous insulation through 13mm single-layer plasterboard wall. Protecta FR Acrylic Sealant depth 12.5mm both sides of wall. No backing. Zero smoke leakage up to 200Pa. Max FRR -/60/45
System ID FC261
Blank seal in plasterboard wall. Protecta FR Acrylic to 12.5mm each side of wall backed with 20mm stone wool. Aperture up to 300 x 300mm or equivalent. Zero smoke leakage up to 200Pa. Max FRR -/120/120
System ID FC118
Cables (electrical, fibre optic, data) single or bundles up to 100mm diam through a plasterboard wall. Protecta FR Acrylic Sealant depth 12.5 to 25mm both sides. Max aperture size 300x300mm or equivalent. Cables up to 21mm also approved for penetrations in linear gap seals. Zero smoke leakage up to 200Pa. Max FRR -/120/120
System ID FC468
Conduit, flexible or rigid, (PVC, PE or PP) up to 40mm through a plasterboard wall, partially or completely filled with cables (electrical, fibre optic, data) up to 21mm diam. Protecta FR Acrylic Sealant depth 25mm both sides. Annular space 10-30mm. Zero smoke leakage up to 200Pa. Max FRR -/120/120
System ID FC119
Metallic pipe with continuous non-combustible insulation (Steel to 324mm, Copper to 54mm, Alupex to 75mm) through a plasterboard wall. Protecta FR Acrylic Sealant depth min 12.5mm both sides backed with stone wool (or just 25mm Acrylic). Max hole size 300x300mm. Annular min 10mm. Zero smoke leakage up to 200Pa. Max FRR -/120/120
System ID FC121
Metal pipe (Steel to 219mm, Copper to 54mm, Alupex to 75mm) through a plasterboard wall. Protecta FR Acrylic Sealant depth 12.5mm both sides with stone wool backing. Max aperture 300x300mm. Annular space min 10mm. Zero smoke leakage up to 200Pa. Max FRR -/120/120
System ID FC365
Metallic pipe with elastomeric combustible insulation or non-combustible insulation (steel up to 165mm diam, copper to 54mm, alupex to 75mm) through a plasterboard wall. Protecta FR Acrylic Sealant depth min 25mm both sides, some with mineral wool backing. Max hole size 300x300mm. Zero smoke leakage up to 200Pa. Max FRR -/120/120
System ID FC333
Bare metal pipe (Steel to 219mm, Copper to 54mm, Alupex to 75mm diam) through a plasterboard wall. Protecta FR Acrylic Sealant depth 12.5mm both sides with stone wool backing. Max aperture 300x300mm. Annular space min 10mm. Zero smoke leakage up to 200Pa. Max FRR -/120/-
System ID FC618
Plastic pipe up to 32mm (PVC, PE, PE-HD, PP, PEX, PP-R, etc) through a plasterboard wall, Protecta FR Acrylic Sealant depth 25mm both sides of wall. No backing required. Zero smoke leakage up to 200Pa. Max FRR -/120/120
System ID FC135
Blank seal up to 180mm diam in 100mm solid timber or CLT wall. Acrylic sealant 25mm to each side of wall backed with 25mm stone or mineral wool. Zero smoke leakage up to 200Pa. Max FRR -/120/120
System ID FC136
Cables up to 50mm diam (electrical, data or fibre optic) single or bundles up to 100mm through a 100mm solid timber or CLT wall. Protecta FR Acrylic Sealant 25mm each side backed with mineral wool. Zero smoke leakage up to 200Pa. Max FRR -/90/90
System ID FC137
Metal pipes (Steel to 273mm, Copper to 54mm, Alupex to 75mm) with interrupted insulation through a 100mm solid timber or CLT wall. FR Acrylic 25mm each side backed with stone wool. Max aperture 293mm (steel) or 180mm (copper/alupex). Zero smoke leakage up to 200Pa. Max FRR -/90/90
System ID FC314
Metal pipes (Steel to 273mm, Copper to 54mm, Alupex to 75mm) with no insulation through a 100mm solid timber or CLT wall. FR Acrylic 25mm each side backed with stone wool. Max aperture 293mm (steel) or 180mm (copper/alupex). Zero smoke leakage up to 200Pa. Max FRR -/90/-
System ID FC109
Metallic pipe with elastomeric combustible insulation or non-combustible insulation (steel up to 114mm diam, copper to 54mm, alupex to 75mm) through a 100mm solid timber or CLT wall. Protecta FR Acrylic Sealant depth min 25mm both sides with mineral wool backing. Annular space 10-30mm. Zero smoke leakage up to 200Pa. Max FRR -/60/45
System ID FC108
Plastic pipe up to 32mm (PVC, PE, PE-HD, PP, PEX, PP-R, etc) through a 100mm solid timber or CLT, Protecta FR Acrylic sealant depth 25mm both sides of wall with mineral wool backing. Zero smoke leakage up to 200Pa. Max FRR -/90/90
System ID FC262
Blank seal up to 300mm x 300mm in 100mm concrete floor. Protecta FR Acrylic to top side of floor or top and bottom for higher rating. Zero smoke leakage up to 200Pa. Max FRR -/240/240
System ID FC123
Single cable (electrical, dats, fibre optic) up to 21mm diam through a 100mm concrete/AAC floor. Protecta FR Acrylic Sealant depth 25mm one side only with mineral wool backing. Max hole size 300x300mm or 100mm linear joint. Zero smoke leakage up to 200Pa. Max FRR -/120/90
System ID FC636
Single cable (electrical, dats, fibre optic) up to 21mm diam through a composite concrete/AAC floor (min topping 50mm). Protecta FR Acrylic Sealant depth 25mm one side only with mineral wool backing. Max hole size 300x300mm or 100mm linear joint. Zero smoke leakage up to 200Pa. Max FRR -/120/90
System ID FC124
Cables (all types of insulated electric cables with copper or aluminium core, fibre optic cables, communication cables) up to 80mm diam single or 100mm bundles) through a concrete floor min 100mm thick. Protecta FR Acrylic Sealant depth 15mm both sides. Max hole size 300x300mm. Zero smoke leakage up to 200Pa. Max FRR -/120/120
System ID FC466
Conduit, flexible or rigid, (PVC, PE or PP) up to 40mm diam with or without cables (all types of insulated electric cables, fibre optic cables, communication cables, up to 21mm diam) through a concrete floor min 100mm thick. Protecta FR Acrylic Sealant depth 25mm both sides with 25mm stone wool backing. Min 10mm annular, max hole size 300x300mm. Zero smoke leakage up to 200Pa. Max FRR -/240/240
System ID FC617
Plastic pipe (PVC, PE, HDPE, PEX, PP, PP-R, etc) through a concrete floor min 100mm thick. Protecta FR Acrylic Sealant depth 25mm both sides with 25mm stone wool backing. Min 10mm annular, max hole size 300x300mm. Zero smoke leakage up to 200Pa. Max FRR -/240/240
System ID FC125
Single insulated (interrupted) metallic pipe (copper up to 54mm, steel up to 219mm, alupex up to 75 diam) through a concrete floor min 100mm thick. Protecta FR Acrylic Sealant depth 15-25mm one side only or anywhere inbetween. Max aperture 300x300mm or 100mm linear gap. Zero smoke leakage up to 200Pa. Max FRR -/240/240
System ID FC637
Single insulated (interrupted) metallic pipe (copper up to 54mm, steel up to 219mm, alupex up to 75 diam) through a composite floor. Protecta FR Acrylic Sealant depth 15-25mm with mineral wool backing. Max aperture 300x300mm or 100mm linear gap. Zero smoke leakage up to 200Pa. Max FRR -/240/240
System ID FC335
Single bare metallic pipe (copper up to 54mm, steel up to 324mm, alupex up to 75mm diam) through a concrete floor min 100mm thick. Protecta FR Acrylic Sealant depth 15-25mm one side only or anywhere inbetween. Max aperture 300x300mm or 100mm linear gap. Zero smoke leakage up to 200Pa. Max FRR -/240/-
System ID FC638
Single bare metallic pipe (copper up to 54mm, steel up to 324mm, alupex up to 75mm diam) through a composite floor. Protecta FR Acrylic Sealant depth 15-25mm with stone wool backing. Max aperture 300x300mm or 100mm linear gap. Zero smoke leakage up to 200Pa. Max FRR -/240/-
System ID FC302
Metal pipe with continuous non-combustible insulation (Steel up to 324mm, Copper up to 54mm, Alupex up to 75mm diam) through a 100mm concrete floor. Protecta FR Acrylic Sealant depth 25mm with mineral wool backing to top of floor only. Max seal size 300 x 300mm. Zero smoke leakage up to 200Pa. Max FRR -/240/240
System ID FC260
Metal pipe (Steel to 324mm, Copper to 54mm, Alupex to 75mm) through a composite floor min 73mm. Protecta FR Acrylic to 25mm backed with 48mm stone wool. Zero smoke leakage up to 200Pa. Max FRR -/240/240
System ID FC298
Single insulated (interrupted) metallic pipe (steel up to 219mm diam) through a 100mm concrete floor. Max aperture 300x300mm or 100mm linear gap. Protecta FR Acrylic Sealant depth 15mm both sides with stone wool backing. Zero smoke leakage up to 200Pa. Max FRR -/240/120
System ID FC300
Single non-insulated metallic pipe (copper 54mm, steel 219mm) through a concrete floor down to 100mm. Protecta FR Acrylic Sealant depth 15-25mm both sides. Up to 300x300 seal size or 100mm linear gap.. Zero smoke leakage up to 200Pa. Max FRR -/240/-
System ID FC299
Single metallic pipe (steel up to 165mm, copper up to 54mm, alupex up to 75mm) with elastomeric or phenolic foam combustible insulation or any non-combustible insulation through a concrete/AAC floor min 100mm thick. Protecta FR Acrylic Sealant depth 25mm both sides with mineral wool backing. Zero smoke leakage up to 200Pa. Max FRR -/180/120
System ID FC413
Blank seal in a 150mm solid timber or CLT floor. Protecta FR Acrylic Sealant depth 25mm with 25mm stonewool backing. Max 220mm diameter. Zero smoke leakage up to 200Pa. Max FRR -/120/120
System ID FC411
Cables (all types of insulated electric cables with copper or aluminium core, fibre optic cables, communication cables) up to 50mm diam single or 100mm bundles through a solid timber or CLT floor min 150mm thick. Protecta FR Acrylic Sealant depth 25mm both sides. Max hole size 220mm diameter. Zero smoke leakage up to 200Pa. Max FRR -/120/120
System ID FC414
Metal pipe (Steel to 273mm, Copper to 54mm, Alupex to 75mm) with interrupted insulation, through a 150mm solid timber or CLT floor. Protecta FR Acrylic 25mm top and bottom with mineral wool backing. Aperture up to 293mm diam. Zero smoke leakage up to 200Pa. Max FRR -/120/120
System ID FC415
Bare metal pipe (Steel to 273mm, Copper to 54mm, Alupex to 75mm) through a 150mm solid timber or CLT floor. Protecta FR Acrylic 25mm top and bottom with mineral wool backing. Max aperture 293mm diam (steel) or 220mm diam (copper, alupex). Zero smoke leakage up to 200Pa. Max FRR -120/-
System ID FC416
Plastic pipes up to 32mm diam (PVC, PE, PE-HD, PEX, PP, PP-R, etc) through a 150mm solid timber or CLT floor. Protecta FR Acrylic Sealant depth 25mm top and bottom with mineral wool backing. Zero smoke leakage up to 200Pa. Max FRR -/120/120
System ID FC443
Service Penetration: Blank seal up to 160mm diameterSubstrate: Concrete flat slab floor, min. 100mm thicknessMax FRR: -/240/120
System ID FC146
Service Penetration: Combustible pipe up to 400mm (PVC, PP, PE, PEX, HDPE, PP-R, etc)Substrate: Concrete flat slab floor, min. 100mm thicknessMax FRR: -/240/120
System ID FC444
Service Penetration: Plastic pipe 32-160mm (PVC, PP, PEX, PE, PP-R, etc)Substrate: Concrete flat slab floor, min 100mm thickMax FRR: -/240/240
System ID FC438
Service Penetration: Plastic pipes up to 160mm (PVC, PE, HDPE, PEX, PP, PP-R, etc)Substrate: Composite floorMax FRR: -/240/240
System ID FC440
Service Penetration: Conduits (PVC, PE, or PEX), rigid or flexible, up to 32 mm, single or bundles to 160 mm.Substrate: Concrete flat slab, min. 100mm thickMax FRR: -/90/90
System ID FC442
Service Penetration: Cable bundles up to 160mm (electrical, data or fibre optic) Substrate: Concrete flat slab, min. 100mm thickMax FRR: -/180/180
System ID FC441
Service Penetration: Insulated pipes (Copper or steel up to 54mm, Alupex to 75mm, PP/PE up to 160mm) with combustible or non-combustible insulationSubstrate: Concrete flat slab, min. 100mm thickMax FRR: -/180/180
System ID FC147
Service Penetration: Combustible pipe up to 400mm (PVC, PP, PE, PEX, HDPE, PP-R, Acoustic, etc)Substrate: CLT or solid timber floor, min. 150mm thickMax FRR: -/240/240
System ID FC439
Service Penetration: Conduits (PVC, PE, or PEX), rigid or flexible, up to 32 mm, single or bundles to 160 mm.Substrate: CLT or solid timber floor, min. 150mm thickMax FRR: -/90/90
System ID FC595
Service Penetration: Cable bundles up to 160mm (electrical, data or fibre optic)Substrate: CLT or solid timber floor, min. 150mm thickMax FRR: -/180/180
System ID FC596
Service Penetration: Insulated pipes (Copper or steel up to 54mm, Alupex to 75mm, PP/PE to 160mm) with combustible or non-combustible insulationSubstrate: CLT or solid timber floor, min. 150mm thickMax FRR: -/180/180
System ID FC436
Service Penetration: Blank seal up to 160mmSubstrate: 2 x 12.5mm Plasterboard or concrete wall, min. 100mm thickMax FRR: -/120/120
System ID FC541
Service Penetration: Combustible pipe 32-160mm (PVC, PE, HDPE, PEX, PP, PP-R, etc)Substrate: 1 x 13mm Plasterboard or concrete wall, min.75mm thickMax FRR: -/60/60
System ID FC144
Service Penetration: Combustible pipe 32-400mm (PVC-U, PVC-C, PE, HDPE, PEX, PP, PP-R, PP-MV etc)Substrate: 2 x 12.5mm Plasterboard or concrete wall, min. 100mm thickMax FRR: -/120/120
System ID FC432
Service Penetration: Low-noise waste pipes (mineral-reinforced PP) and domestic water pipes (PP-R, PP-RP, PP-RCT), 32–160 mmSubstrate: 2 x 12.5mm Plasterboard or concrete wall, min. 100mm thickMax FRR: -/120/120
System ID FC598
Service Penetration: Plastic pipes (PVC, PE, HDPE, PEX, PP, PP-R, PP-MV, PP-H) up to 40mm, in mixed bundles up to 160mmSubstrate: 2 x 12.5mm Plasterboard or concrete wall, min. 100mm thickMax FRR: -/90/90
System ID FC434
Service Penetration: Cables, single or bundled, up to 160mmSubstrate: 2 x 12.5mm Plasterboard or concrete wall, min. 100mm thickMax FRR: -/120/60
System ID FC597
Service Penetration: Rigid or flexible plastic conduits up to 40mm, single or bundled, with or without cables up to 21mm in mixed bundles up to 160mmSubstrate: 2 x 12.5mm plasterboard or concrete wall, min. 100mm thickMax FRR: -/90/90
System ID FC599
Service Penetration: PE or PP plastic pipes up to 160mm with combustible or non-combustible insulationSubstrate: 2 x 12.5mm plasterboard or concrete wall, min. 100mm thickMax FRR: -/120/120
System ID FC437
Service Penetration: Steel or Copper pipes up to 54mm or Alupex pipes up to 75mm with combustible or non-combustible insulationSubstrate: 2 x 12.5mm plasterboard or concrete wall, min. 100mm thickMax FRR: -/120/90
System ID FC433
Protecta FR Collars have been specifically tested and approved for use in oversize applications. They provide flexibility in situations where pipes or services are not installed square to the wall or floor, or where apertures are larger than standard.
System ID FC602
Service Penetration: Combustible pipe 32-400mm (PVC, PE, HDPE, PEX, PP, PP-R, PP-MV etc)Substrate: CLT or solid timber wall, min. 100mm thickMax FRR: -/120/120
System ID FC603
Service Penetration: Low-noise waste pipes (mineral-reinforced PP) and domestic water pipes (PP-R, PP-RP, PP-RCT), 32–160 mmSubstrate: CLT or solid timber wall, min. 100mm thickMax FRR: -/120/120
System ID FC604
Service Penetration: Plastic pipes (PVC-C, PVC-U, PE, HDPE, PEX, PP, PP-R, PP-MV, PP-H) up to 40mm in mixed bundles up to 160mmSubstrate: CLT or solid timber wall, min. 100mm thickMax FRR: -/90/90
System ID FC605
Service Penetration: Cables, single or bundled, up to 160mmSubstrate: CLT or solid timber wall, min. 100mm thickMax FRR: -/120/60
System ID FC606
Service Penetration: Rigid or flexible plastic conduits up to 40mm, single or bundled, with or without cables up to 21mm in mixed bundles up to 160mmSubstrate: CLT or solid timber wall, min. 100mm thickMax FRR: -/90/90
System ID FC607
Service Penetration: PE or PP plastic pipes up to 160mm with combustible or non-combustible insulationSubstrate: CLT or solid timber wall, min. 100mm thickMax FRR: -/120/120
System ID FC608
Service Penetration: Steel or Copper pipes up to 54mm or Alupex pipes up to 75mm with combustible or non-combustible insulationSubstrate: CLT or solid timber wall, min. 100mm thickMax FRR: -/120/90
System ID FC550
Service Penetration: Combustible pipe 32-160mm (PVC, PE, PE-HD, PEX, PP, PP-R, etc)Substrate: Concrete wall, min. 75 - 150mm thickMax FRR: -/240/180
System ID FC145
Service Penetration: Combustible pipe 32-400mm (PVC, PE, PE-HD, PEX, PP, PP-R, etc)Substrate: Concrete wall, min. 100mm thickMax FRR: -/240/240
System ID FC610
Service Penetration: Low-noise waste pipes (mineral-reinforced PP) and domestic water pipes (PP-R, PP-RP, PP-RCT), 32–160 mmSubstrate: Concrete wall, min. 100mm thickMax FRR: -/120/120
System ID FC611
Service Penetration: Plastic pipes (PVC-C, PVC-U, PE, HDPE, PEX, PP, PP-R, PP-MV, PP-H) up to 40mm in mixed bundles up to 160mmSubstrate: Concrete wall, min. 100mm thickMax FRR: -/90/90
System ID FC612
Service Penetration: Cables, single or bundled, up to 160mmSubstrate: Concrete wall, min. 100mm thickMax FRR: -/120/60
System ID FC613
Service Penetration: Rigid or flexible plastic conduits up to 40mm, single or bundled, with or without cables up to 21mm in mixed bundles up to 160mmSubstrate: Concrete wall, min. 100mm thickMax FRR: -/90/90
System ID FC614
Service Penetration: PE or PP plastic pipes up to 160mm with combustible or non-combustible insulation Substrate: Concrete wall, min. 100mm thickMax FRR: -/120/120
System ID FC615
Service Penetration: Steel or Copper pipes up to 54mm or Alupex pipes up to 75mm with combustible or non-combustible insulationSubstrate: Concrete wall, min. 100mm thickMax FRR: -/120/90
System ID FC152
Service Penetration: Single or double (including plastic) electric flush boxSubstrate: 2 x 13mm Plasterboard wall, min 100mm thickMax FRR: -/120/120
System ID FC312
Service Penetration: Single cable up to 80mmSubstrate: 2 x 13mm Plasterboard or concrete wall, min. 100mm thickMax FRR: -/120/120
System ID FC349
Service Penetration: Electric cable bundle up to 50mmSubstrate: 2 x 13mm Plasterboard or concrete wall, min. 100mm thickMax FRR: -/120/120
System ID FC352
Service Penetration: Uninsulated pipes (steel, copper or alupex)Substrate: 2 x 13mm Plasterboard or concrete wall, min. 100mm thickMax FRR: -/120/120
System ID FC353
Service Penetration: Metal pipes (steel, copper or alupex) with local interrupted insulationSubstrate: 2 x 13mm plasterboard or concrete wall, min. 100mm thickMax FRR: -/120/120
System ID FC354
Service Penetration: Metal pipes (steel, copper or alupex) with continuous insulationSubstrate: 2 x 13mm plasterboard or concrete wall, min.100mm thickMax FRR: -/120/120
System ID FC403
Service Penetration: Electric cable bundle up to 50mmSubstrate: Concrete wall, min. 100mm thickMax FRR: -/120/120
System ID FC404
Service Penetration: Uninsulated pipes (steel, copper or alupex)Substrate: Concrete wall, min 100mm thickMax FRR: -/120/120
System ID FC405
Service Penetration: Metal pipes (steel, copper or alupex) with local interrupted insulationSubstrate: Concrete wall, min 100mm thickMax FRR: -/120/120
System ID FC406
Service Penetration: Metal pipes (steel, copper or alupex) with continuous insulationSubstrate: Concrete wall, min 100mm thickMax FRR: -/120/120
System ID FC355
Service Penetration: Electric cables, single up to 80mm or bundles up to 50mmSubstrate: Concrete flat slab floor, min 150mm thickMax FRR: -/240/240
System ID FC356
Service Penetration: Electric cables, single up to 80mm or bundles up to 75mmSubstrate: Concrete flat slab floor, min 150mm thickMax FRR: -/120/60
System ID FC358
Service Penetration: Metal pipe (Copper, steel & alupex)Substrate: Concrete flat slab floor, min 150mm thickMax FRR: -/240/240
System ID FC357
Service Penetration: Metal pipe (copper or steel)Substrate: Concrete flat slab floor, min 150mm thickMax FRR: -/120/120
System ID FC359
Service Penetration: Metal pipe (copper, steel or alupex) with interrupted insulation Substrate: Concrete flat slab floor, min 150mm thickMax FRR: -/240/240
System ID FC360
Service Penetration: Metal pipe (copper, steel or Alupex) with continuous insulationSubstrate: Concrete flat slab floor, min 150mm thickMax FRR: -/240/240
System ID FC584
Metal pipe (Steel to 324mm, Copper to 54mm, Alupex to 75mm) with combustible insulation through a core-drilled concrete wall min 100mm thick. Protecta FR Wrap to both sides of wall. Max annular space 30mm. Fill all remaining annular space with Protecta FR Acrylic to full depth of wall. Max FRR -/120/120
System ID FC571
Plastic pipes (PVC-U, HDPE, PEX, PP, PPR, Acoustic, Aquatherm, etc) and bundles of mixed 32mm plastic pipes through a core-drilled concrete wall min 100mm thick. Protecta FR Wrap to both sides of wall. Max annular space 30mm. Fill all remaining annular space with Protecta FR Acrylic to full depth of wall. Max FRR -/240/240
System ID FC101
Plastic conduit (PVC, PE, PEX, PP, PP-R, etc) through a core-drilled 100mm concrete wall, Two layers of Protecta FR Wrap to each side. Max annular gap 30mm. Finish with Protecta FR Acrylic to full depth of wall. Max FRR -/120/90
System ID FC583
Plastic pipes (PE, HDPE, PEX, PP, PPR, etc) with combustible insulation through a core-drilled concrete wall min 100mm thick. Protecta FR Wrap to both sides of wall. Max annular space 30mm. Fill all remaining annular space with Protecta FR Acrylic to full depth of wall. Max FRR -/60/60
System ID FC575
Metal pipes with combustible insulation (steel 40mm-165mm, copper to 54mm, Alupex to 75mm) through a 100mm core-drilled concrete floor. Max annular gap 30mm. Protecta FR Pipe Wrap 50mm fitted at bottom of seal. Fill any remaining annular space to a depth of 15mm with Protecta FR Acrylic sealant backed with 25mm stone wool (or fill with 40mm Acrylic). Max FRR -/240/120
System ID FC585
Plastic pipe (PVC-U up to 110mm) through a 100mm core-drilled concrete floor. Max annular gap 30mm. Protecta FR Pipe Wrap 50mm fitted at bottom of seal. Fill any remaining annular space to a depth of 15mm with Protecta FR Acrylic sealant backed with 25mm stone wool (or fill with 40mm Acrylic). Max FRR -/90/90
System ID FC392
Service Penetration: Timber framed wall fire-stopped with Protecta Infill Naked WallSubstrate: Min. 90mm x 45mm Timber stud wall, studs at max. 1365mm centresMax FRR: -/45/45
System ID FC393
Service Penetration: Steel stud wall fire-stopped with Protecta Infill Naked WallSubstrate: Min. 64mm steel stud wall, studs at max. 600mm centresMax FRR: -/60/60
System ID FC253
Blank seal in concrete wall up to 1200mm high x unlimited width. Protecta FR Board 60mm 2-s, one sheet friction-fitted anywhere within aperture. Seal edges with FR Acrylic. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/240/90
System ID FC311
A blank seal is installed between the top of a concrete or plasterboard wall and the underside of the construction substrate above, which may be flat, sloped, or serrated (e.g. Comflor, Traydec). FR Board is friction-fitted at any position within the aperture. The system accommodates an unlimited width and a vertical height of up to 1200 mm. It is smoke-safe, with a maximum smoke leakage of 0.1 m³/h at 200 Pa. The maximum fire resistance rating (FRR) achieved is -/240/90.
System ID FC176
Cable (single up to 21mm, any position in board) through a concrete wall min 75mm thick with Protecta FR Board 60mm 2-sided friction fitted anywhere in wall cavity. Finish with Protecta FR Acrylic sealant. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/240/90
System ID FC178
Metal pipe (interrupted or continuous insulation, copper to 54mm, steel to 325mm, Alupex to 75mm) through a concrete wall min 75mm thick. Protecta FR Board 60mm 2-sided to one side of wall only. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/240/120
System ID FC351
Metal pipes (Uninsulated, Copper to 54mm, Steel to 325mm, Alupex to 75mm) through a concrete wall min 75mm thick. Protecta FR Board 60mm 2-sided to one side of wall only. Finish with Protecta FR Acrylic sealant. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/240/-
System ID FC276
Service Penetration: Steel or copper pipes up to 54mm or Alupex pipes up to 75mm with combustible or non-combustible insulationSubstrate: Concrete wall, min. 100mm thickMax FRR: -/60/60
System ID FC363
Metal pipe (continuous combustible or non-combustible insulation, steel to 165mm) through a concrete wall min 75mm thick. Protecta FR Board 60mm 2-sided to one side of wall only or anywhere in between. Protecta FR Pipe Wrap single layer. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/120/30
System ID FC104
Service Penetration: Plastic pipe (PVC, PE, PEX, HDPE, etc) up to 160mmSubstrate: Concrete wall, min. 100mm thickMax FRR: -/120/60
System ID FC252
Blank seal in concrete or masonry wall up to 1200mm high x unlimited width. Wall thickness minimum 75mm. Protecta FR Board 60mm double-sided friction fitted to both sides of wall. Pattress fit option available. Seal edges with FR Acrylic. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/240/240
System ID FC310
Cables (single or bundles) and conduits through a concrete or masonry wall min 75mm thick. Protecta FR Board 60mm or 50mm to both sides of wall. Finish with Protecta FR Acrylic sealant. Pattress fit option available. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/240/180
System ID FC175
Cable trays or conduit through a concrete wall min 75mm thick. Protecta FR Board 60mm or 50mm to both sides of wall. Finish with Protecta FR Acrylic sealant. Pattress fit option available. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/240/180
System ID FC177
Metal pipes with interrupted insulation (Steel to 219mm, Copper to 54mm, Alupex to 16mm) through a concrete wall min 75mm thick.. Protecta FR Board 60mm or 50mm to both sides of wall. Finish with Protecta FR Acrylic. Unlimited width x 1200mm high. Pattress fit option available. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/240/180
System ID FC569
Metal pipes with no insulation (Steel to 324mm, Copper to 54mm, Alupex to 75mm) through a concrete wall min 75mm thick. Protecta FR Board 60mm or 50mm to both sides of wall. Finish with Protecta FR Acrylic. Unlimited width x 1200mm high. Pattress fit option available. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/240/-
System ID FC275
Metal pipes (Steel up to 324mm, Copper up to 54mm, Alupex up to 75mm, continuous sustained insulation) through a concrete wall min 75mm thick. Protecta FR Board 60mm or 50mm to both sides of wall. Pattress fit option available. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/240/180
System ID FC234
Metal pipes with continuous combustible or non-combustible insulation (Steel to 324mm, Copper to 54mm, Alupex to 75mm) through a concrete wall min 75mm thick. Protecta FR Board 50mm and Protecta FR Wrap to each side of wall. Finish with Protecta FR Acrylic sealant. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR - /120/120
System ID FC102
Plastic conduits (PVC, PE, PE-HD, PEX, PP, PP-R) up to 110mm fully or partially filled with cables up to 14mm diam or smaller conduits in bundles up to 110mm diam through a concrete, AAC or masonry wall min 75mm thick. Protecta FR Board 50mm 1-S each side. Double layer Protecta FR Pipe Wrap around conduit each side of wall. Finish with Protecta FR Acrylic sealant. Pattress option. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/120/90
System ID FC570
Plastic pipes (PVC-U, HDPE, PEX, PP, PPR and specialty acoustic and thermal) and bundles of mixed 32mm plastic pipes through a concrete wall min thickness 75mm. Protecta FR Board 60mm or 50mm and Protecta FR Wrap to both sides of wall. Protecta FR Acrylic to finish. Pattress fit option available. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/240/240
System ID FC103
Plastic pipes (PP, PE, PEX, PE-HD, PP-R) up to 160mm diam with combustible Elastomeric or PE Foam insulation (9 - 50mm thick) or non-combustible insulation through a concrete, AAC or masonry wall min 75mm thick. Protecta FR Board 50mm 1-S each side. Protecta FR Pipe Wrap around pipe insulation each side of wall. Finish with Protecta FR Acrylic sealant. Pattress fix option available. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/60/60.
System ID FC254
Blank seal in concrete wall up to 600 x 600mm. Protecta FR Board 60mm double-sided on each side of wall, protruding up to 30mm. Rating -/240/180. Seal edges and exposed faces with Protecta FR Acrylic.
System ID FC255
Blank seal in concrete wall up to 600 x 600mm. Protecta FR Board 60mm 2-S on each side of wall, pattress fixed 50mm overlap, with Protecta FR Acrylic sealant. Max FRR -/240/180.
System ID FC181
Cables (single, bundles or cable trays) through a concrete wall. Protecta FR Board 60mm 2-sided to both external faces of wall, pattress fixed, with Protecta FR Acrylic sealant. Max FRR -/240/240
System ID FC408
Protecta FR Board and Protecta EX Mortar may be used to provide a penetration seal for mixed services within the same aperture. Services can include cables, cable trays, metallic pipes, composite pipes and plastic pipes, with and without insulation.
System ID FC256
Blank seal in 150mm concrete floor up to 2400 x 1200mm. Two layers Protecta FR Board 60mm double-sided with Protecta FR Acrylic sealant. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/180/180
System ID FC182
Cables (single, bundles or cable trays) or PVC Conduit through a 150mm concrete floor. Two layers Protecta FR Board 60mm 2-S with Protecta FR Acrylic sealant. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/120/120
System ID FC257
Blank seal in 100mm concrete floor up to 2400 x 1200mm (or linear gap up to 800mm). One layer Protecta FR Board 60mm double-sided anywhere in aperture. Seal edges Protecta FR Acrylic. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/120/90
System ID FC183
Cables (single, bundled or cable trays) and conduit through a 100mm concrete floor. One Protecta FR Board 60mm 2-sided positioned anywhere in floor. Finish with Protecta FR Acrylic sealant. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/90/30
System ID FC185
Steel pipe (interrupted insulation, mild or stainless steel up to 219mm) through a concrete floor min 120mm. Two layers of Protecta FR Board 60mm 2-sided fitted together anywhere within the floor. Finish with Protecta FR Acrylic sealant. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/240/240
System ID FC573
Steel pipe (no insulation, mild or stainless steel up to 219mm) through a concrete floor min 120mm. Two layers of Protecta FR Board 60mm 2-sided fitted together anywhere within the floor. Finish with Protecta FR Acrylic sealant. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/240/-
System ID FC186
Metallic pipe (interrupted insulation, copper to 54mm, steel to 219mm, PEX/AL/HDPE to 75mm) through a 100mm concrete floor. One layer Protecta FR Board 60mm 2-sided anywhere in floor space. Finish with Protecta FR Acrylic sealant. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/240/240
System ID FC574
Metallic pipe (no insulation, copper to 54mm, steel to 219mm, PEX/AL/HDPE to 75mm) through a 100mm concrete floor. One layer Protecta FR Board 60mm 2-sided anywhere in floor space. Finish with Protecta FR Acrylic sealant. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/240/-
System ID FC167
Metal pipes with continuous combustible or non-combustible insulation (steel 40mm-165mm, copper to 54mm, Alupex to 75mm) through a 120mm concrete floor. Two Protecta FR Boards 60mm 2-sided fitted anywhere in the aperture, together or separate. Protecta FR Pipe Wrap 50mm fitted at bottom of seal. Finish with Protecta FR Acrylic sealant. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/240/120
System ID FC165
Plastic pipes (PVC-U to110mm) through a 100mm concrete floor. Protecta FR Board 2-sided (50mm or 60mm) in middle of floor. Protecta FR Pipe Wrap 50mm double layer. Finish with Protecta FR Acrylic sealant. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/90/90
System ID FC549
Linear gap in solid timber or CLT floor (up to 400mm wide, unlimited length). Protector FR Board friction fitted into gap and second FR Board pattress fitted to soffit. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/90/90
System ID FC576
Cables (single, bundled or cable trays) and conduit through a 150mm solid timber or CLT floor. One Protecta FR Board 50mm or 60mm friction fitted within aperture and second FR Board overlapping the aperture by 100mm all sides. Finish with Protecta FR Acrylic sealant. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/90/60
System ID FC577
Metallic pipe (interrupted insulation, copper to 54mm, steel to 273mm, Alupex to 75mm) through a 150mm solid timber or CLT floor. One layer Protecta FR Board 50mm or 60mm within the aperture with a second FR Board overlapping 100mm. Finish with Protecta FR Acrylic sealant. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/90/90
System ID FC578
Metallic pipe (bare - no insulation, copper to 54mm, steel to 273mm, Alupex to 75mm) through a 150mm solid timber or CLT floor. One layer Protecta FR Board 50mm or 60mm within the aperture with a second FR Board overlapping 100mm. Finish with Protecta FR Acrylic sealant. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/90/-
System ID FC258
Blank or linear gap seal in plasterboard wall up to 1200mm high x unlimited width. One layer Protecta FR Board 50mm 1-S to each side of wall. Minimum single layer 13mm plasterboard. Seal with Protecta FR Acrylic. Pattress fix option available. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/120/120
System ID FC601
Blank or linear gap seal up to 1200mm high x unlimited width from plasterboard wall to rigid substrate (concrete, AAC, masonry, steel, etc). One layer Protecta FR Board 50mm 1-S to each side of wall. Minimum single layer 13mm plasterboard. Seal with Protecta FR Acrylic. Pattress fix option available. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/120/120
System ID FC580
Cables, single or bundled through a plasterboard wall, including single layer plasterboard walls. Protecta FR Board 50mm 1-S (or 60mm 2-S) to both sides of wall. Pattress fix option available. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/60/60
System ID FC188
Cables and conduits on trays through a plasterboard wall, including single layer plasterboard walls. Protecta FR Board 50mm 1-S (or 60mm 2-S) to both sides of wall. Pattress fix option available. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/60/60
System ID FC272
Metal pipes (continuous non-combustible insulation, steel to 324mm, copper to 54mm, Alupex to 75mm) through a plasterboard wall. Protecta FR Board 50mm 1-S to each side of wall. Pattress fixed option available. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/120/120
System ID FC274
Metal pipes with continuous combustible or non-combustible insulation (steel to 324mm, copper to 54mm, Alupex to 75mm) through a plasterboard wall. Protecta FR Board 50mm 1-S each side. Protecta FR Pipe Wrap around pipe insulation. Finish with Protecta FR Acrylic sealant. Pattress fix option available. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/120/120
System ID FC189
Metal pipes with insulated interrupted (steel to 219mm, copper to 54mm, Alupex to 75mm) through a plasterboard wall. Protecta FR Board 50mm 1-sided to both sides of wall. Finish with Protecta FR Acrylic. Pattress fix option available. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/120/120
System ID FC313
Metallic pipes (un-insulated, steel to 324mm, copper to 54mm, Alupex to 75mm) through a plasterboard wall. Protecta FR Board 50mm 1-sided to both sides of wall. Finish with Protecta FR Acrylic. Pattress fix option available. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/120/-
System ID FC559
Plastic conduits (PVC, PE, PE-HD, PEX, PP, PP-R) up to 110mm fully or partially filled with cables up to 14mm diam or smaller conduits in bundles up to 110mm diam through a plasterboard wall. Protecta FR Board 50mm 1-S each side. Double layer Protecta FR Pipe Wrap around conduit each side of wall. Finish with Protecta FR Acrylic sealant. Pattress option. Smoke-safe. Max FRR -/120/90
System ID FC581
Plastic pipes (PVC, PE, PE-HD, PEX, PP, PP-R up to 400mm) or composite pipes (Aquatherm, Uponor Decibel, etc up to 160mm) through a plasterboard wall. Protecta FR Board 50mm or 60mm each side. Protecta FR Pipe Wrap around pipes each side of wall. Finish with Protecta FR Acrylic sealant. Pattress option. Smoke-safe. Max FRR -/120/120
System ID FC364
Plastic pipes (PP, PE, PEX, PE-HD, PP-R) up to 160mm diam with combustible Elastomeric or PE Foam insulation (9 - 50mm thick) or non-combustible insulation through a plasterboard wall. Protecta FR Board 50mm 1-S each side. Protecta FR Pipe Wrap around pipe insulation each side of wall. Finish with Protecta FR Acrylic sealant. Pattress fix option available. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/60/60
System ID FC171
Metal pipes with stone wool continuous insulation (Steel to 324mm, copper to 54mm, Alupex to 75mm) through a plasterboard wall. Protecta FR Board 60mm 2-sided to either side of wall or anywhere inbetween. Finish with Protecta FR Acrylic sealant. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/90/60
System ID FC172
Service Penetration: Plastic pipes (PVC, HDPE, PEX, PP, PP-R, etc) up to 160mmSubstrate: 2 x 12.5mm Plasterboard or concrete wall, min. 100mm thickMax FRR: -/120/60
System ID FC170
Service Penetration: Steel or copper pipes up to 54mm or Alupex pipes up to 75mm with combustible or non-combustible insulationSubstrate: 2 x 12.5mm Plasterboard or concrete wall, min. 100mm thickMax FRR: -/60/60
System ID FC743
Service Penetration: C-Purlin 200mm (3-sided) and 400mm (4-sided)Substrate: 2 x 13mm Plasterboard or concrete wall, min. 144mm thickMax FRR: -/120/120
System ID FC783
Service Penetration: Structural I-beam 250mm (3-sided with wrap, 4-sided with no wrap)Substrate: 2 x 13mm Plasterboard or concrete wall, min. 144mm thickMax FRR: -/120/120
System ID FC409
System ID FC166
Blank or linear gap seal in a solid timber or CLT wall. Protecta FR Board 50mm or 60mm pattress fitted to each side of wall oversailing aperture by 100mm. Fix with 100mm wood screws and penny washers. Finish with Protecta FR Acrylic sealant. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/120/120
System ID FC586
Cables, single or bundled through a 100mm solid timber or CLT wall. Protecta FR Board 50mm 1-S (or 60mm 2-S) pattress-fitted to both sides of wall. Finish with Protecta FR Acrylic sealant. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/60/60
System ID FC587
Cables and conduits on trays through a 100mm solid timber or CLT walls. Protecta FR Board 50mm 1-S (or 60mm 2-S) pattress-fitted to both sides of wall. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/120/90
System ID FC588
Metal pipes with continuous non-combustible insulation (steel to 324mm, copper to 54mm, Alupex to 75mm) through a 100mm solid timber or CLT wall. Protecta FR Board 50mm or 60mm pattress-fitted to each side of wall. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/120/120
System ID FC589
Metal pipes with continuous combustible or non-combustible insulation (steel to 324mm, copper to 54mm, Alupex to 75mm) through a 100mm solid timber or CLT wall. Protecta FR Board 50mm or 60mm pattress-fitted to each side. Protecta FR Pipe Wrap around pipe insulation each side of wall. Finish with Protecta FR Acrylic sealant. Smoke-safe (<0.1m3/h leakage). Max FRR -/120/120
System ID FC590
Metal pipes with insulated interrupted (steel to 219mm, copper to 54mm, Alupex to 75mm) through a 100mm solid timber or CLT wall. Protecta FR Board 50mm or 60mm pattress-fitted to both sides of wall. Finish with Protecta FR Acrylic. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/120/120
System ID FC591
Metallic pipes (un-insulated, steel to 324mm, copper to 54mm, Alupex to 75mm) through a 100mm solid timber or CLT wall. Protecta FR Board 50mm or 60mm pattress-fitted to both sides of wall. Finish with Protecta FR Acrylic. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/120/30
System ID FC592
Plastic conduits (PVC, PE, PE-HD, PEX, PP, PP-R) up to 110mm fully or partially filled with cables up to 14mm diam or smaller conduits in bundles up to 110mm diam through a 100mm solid timber or CLT wall. Protecta FR Board 50mm or 60mm pattress-fitted each side. Double layer Protecta FR Pipe Wrap around conduit each side of wall. Finish with Protecta FR Acrylic sealant. Smoke-safe. Max FRR -/120/90
System ID FC593
Plastic pipes (PVC, PE, PE-HD, PEX, PP, PP-R up to 400mm) or composite pipes (Aquatherm, Uponor Decibel, etc up to 160mm) through a 100mm solid timber or CLT wall. Protecta FR Board 50mm or 60mm pattress-fitted each side. Protecta FR Pipe Wrap around pipes each side of wall. Finish with Protecta FR Acrylic sealant. Smoke-safe (<0.1m3/h smoke leakage at 200Pa). Max FRR -/120/120
System ID FC594
Plastic pipes (PP, PE, PEX, PE-HD, PP-R) up to 160mm diam with continuous combustible Elastomeric or PE Foam insulation (9 - 50mm thick) or non-combustible insulation through a 100mm solid timber or CLT wall. Protecta FR Board 50mm or 60mm pattress-fitted each side. Protecta FR Pipe Wrap around pipe insulation each side of wall. Finish with Protecta FR Acrylic sealant. Smoke-safe. Max FRR -/60/60
System ID FC264
Blank seal in concrete wall. Protecta EX Mortar 50mm with 50mm stone wool backing, anywhere within aperture. Rating -/180/120. Up to 2400mm wide x 1200mm high.
System ID FC194
Cables (single or bundles) and conduits through a concrete wall. Protecta EX Mortar 50mm any position in wall backed by 50mm mineral wool. Max FRR -/180/90
System ID FC342
Cable trays with cables through a concrete wall. Protecta EX Mortar 50mm any position in wall backed by 50mm mineral wool. Max FRR -/180/60
System ID FC265
Blank seal in concrete wall. Protecta EX Mortar 100mm anywhere within aperture. Rating -/240/240. Up to 2400mm wide x 1200mm high.
System ID FC197
Cables (single or bundled) and conduits through a concrete wall. Protecta EX Mortar 100mm any position within the wall. Max FRR -/240/240
System ID FC343
Cable trays through a concrete wall. Protecta EX Mortar 100mm any position within the wall. Max FRR -/240/60
System ID FC195
Metal pipes (insulated sustained mineral wool, steel 219mm) through a concrete wall. Protecta EX Mortar 50mm any position within wall backed by 50mm mineral wool 150kg/m3. Max FRR -/120/90
System ID FC196
Metal pipe (steel, copper, Alupex, interrupted insulation) through a concrete wall. Protecta EX Mortar 50mm any position in wall backed with 50mm mineral wool. Max FRR -/180/120
System ID FC345
Bare metal pipes (steel, copper, Alupex) through a concrete wall. Protecta EX Mortar 50mm any position in wall backed with 50mm mineral wool. Max FRR -/180/-
System ID FC199
Metal pipe (single, insulated interrupted, steel up to 219mm) through a 100mm concrete wall. Protecta EX Mortar 100mm any position in the wall. Max FRR -/240/240
System ID FC346
Metal pipe (uninsulated, steel to 219mm, Copper to 54mm, Alupex to 75mm) through a 100mm concrete wall. Protecta EX Mortar 100mm any position in wall. Max FRR -/240/120
System ID FC344
Metal pipes (combustible or non-combustible insulation sustained, steel up to 165mm) through a concrete wall. Protecta EX Mortar 100mm with Protecta FR Pipe Wraps. Max FRR -/240/60
System ID FC267
Blank seal in 100mm concrete floor. Protecta EX Mortar 50mm backed with 50mm stone wool any position in floor. Rating -/180/180. Up to 2400 x 1200mm.
System ID FC201
Cables (bundles up to 100mm) or PVC Conduits through a concrete floor min 100mm thick. Protecta EX Mortar 50mm, backed by 50mm mineral wool. Max FRR -/180/180
System ID FC336
Cables, wires and PVC Conduits on cable trays through a concrete floor min 100mm thick. Protecta EX Mortar 50mm, backed by 50mm mineral wool. Max FRR -/180/60
System ID FC268
Blank seal in 100mm concrete floor. Protecta EX Mortar 100mm anywhere in the floor. Rating -/240/240. Up to 2400mm x 1200mm aperture.
System ID FC337
Cables or PVC Conduits through a concrete floor or wall min 100mm thick. Protecta EX Mortar 100mm to top, bottom or anywhere inbetween. Max FRR -/180/180
System ID FC567
Conduits (PVC, HDPE, PEX or PP) through a concrete floor or wall min 100mm thick. Protecta EX Mortar 100mm to top, bottom or anywhere in between. Protecta FR Pipe Wrap to bottom of seal. Max FRR -/120/120
System ID FC203
Cables (single or bundled or trays), unsheathed wires and PVC conduits through a concrete floor or wall min 100mm thick. Protecta EX Mortar 100mm any position within the floor. Max FRR -/180/60
System ID FC202
Steel, Copper or Alupex pipe (insulated interrupted, steel to 219mm, copper to 54mm, Alupex to 75mm) through a concrete floor min 100mm thick. Protecta EX Mortar 50mm, backed by 50mm mineral wool. Max FRR -/180/180
System ID FC338
Metallic pipe (continuous insulation, steel to 324mm, copper to 54mm, Alupex to 75mm) through a concrete floor min 100mm thick. Protecta EX Mortar 50mm, backed by 50mm mineral wool. Max FRR -/240/240
System ID FC339
Metallic pipes (uninsulated, steel to 324mm, copper to 54mm, Alupex to 75mm) through a concrete floor min 100mm thick. Protecta EX Mortar 50mm, backed by 50mm mineral wool. Max FRR -/180/120
System ID FC204
Metallic pipe (single, insulated interrupted, steel to 219mm) through a concrete floor or wall min 100mm thick. Protecta EX Mortar 100mm any position within floor. Max FRR -/240/240
System ID FC340
Metallic pipe (uninsulated, steel 219mm, copper to 54mm, Alupex to 75mm) through a concrete floor or wall min 100mm thick. Protecta EX Mortar 100mm any position within floor. Max FRR -/240/120
System ID FC205
Metallic pipes (multiple, combustible insulation sustained, Steel to 324mm, Copper to 54mm, Alupex to 75mm) through a concrete floor or wall min 100mm thick. Protecta EX Mortar 100mm with Protecta FR Pipe Wraps. Max FRR -/240/240
System ID FC206
All types of plastic pipes (PVC, PP, PE, PEX, Aquatherm, Acoustic, Multilayer, etc) through a concrete floor. Protecta EX Mortar 100mm any position within floor with Protecta FR Pipe Wrap to bottom of seal. Min 30mm between pipes or edges. Max FRR -/240/240
System ID FC568
Insulated plastic pipes (PP, HDPE, PEX) through a concrete floor or wall min 100mm thick. Insulation may be combustible (Elastomeric or foam) or non-combustible. Protecta EX Mortar 100mm to top, bottom or anywhere in between. Protecta FR Pipe Wrap to bottom of seal. Max FRR -/240/240
System ID FC407
System ID FC207
Service Penetration: Plastic pipe (single, PP 40mm, PE 40mm & 110mm). PE 110mm requires 1 layer of Protecta FR Pipe Wrap 50mm.Substrate: Concrete flat slab, min. 100mm thickMax FRR: -/120/120Report Page: 76
System ID FC705
Service Penetration: 150mm SHS Column, perpendicular or inclinedSubstrate: CLT (Red Stag) floor, min. 125mm thickMax FRR: -/90/90
System ID FC208
Service Penetration: PVC pipe (multiple) up to 40mmSubstrate: Concrete flat slab, min. 100mm thickMax FRR: -/120/120Report Pages: 77 & 78
System ID FC211
Cables (single, bundles or trays) through a plasterboard wall. Protecta EX Mortar 25mm to both sides of wall, with 50mm mineral wool inbetween. Max FRR -/120/120
System ID FC212
Metallic pipes (multiple, insulated interrupted, Alupex composite up to 75mm, steel up to 219mm, copper up to 54mm) through a plasterboard wall. Protecta EX Mortar 25mm to each side of wall with 50mm mineral wool inbetween. Max aperture 2400x1200mm. Max FRR -/120/120
System ID FC562
Bare metal pipes (multiple, insulated interrupted, Alupex composite up to 75mm, steel up to 219mm, copper up to 54mm) through a plasterboard wall. Protecta EX Mortar 25mm to each side of wall with 50mm mineral wool inbetween. Max aperture 2400x1200mm. Max FRR -/120/-
System ID FC163
Metallic pipes (combustible insulation, steel to 165mm, copper to 54mm, Alupex to 75mm) through a plasterboard wall. Mortar 50mm each side. Protecta FR Pipe Wrap 50mm double layer each side of wall. Max FRR -/120/120
System ID FC348
All Protecta double-sided systems may be used as single-sided systems. See attached letter from Manufacturer.
System ID FC513
Service Penetration: Vertical linear gap, 5mm up to 20mmSubstrate: 1 x 16mm Plasterboard (double stud) or concrete wall, min. 180mm thickMax FRR: -/90/90
System ID FC516
Service Penetration: Horizontal linear gap up to 40mm to underside of concrete floor slab.Substrate: 1 x 16mm Plasterboard (double stud) or concrete wall, min. 180mm thickMax FRR: -/90/90
System ID FC517
Service Penetration: Blank aperture up to 40mmSubstrate: 2 x 13mm Plasterboard or concrete wall, min. 116mm thickMax FRR: -/120/120
System ID FC347
Service Penetration: Vertical gaps up to 20mm Substrate: 2 x 13mm Plasterboard or concrete wall, min. 116mm thickMax FRR: -/120/120
System ID FC512
Service Penetration: Horizontal linear gap up to 40mm to underside of concrete floor slab, with 25mm electric cable bundle (optional)Substrate: 2 x 13mm Plasterboard or concrete wall, min. 116mm thickMax FRR: -/120/120
System ID FC292
Service Penetration: Linear gaps - up to 40mm horizontally and 50mm verticallySubstrate: Concrete wall, min. 180mm thickMax FRR: -/360/360
System ID FC504
Service Penetration: Copper pipe (100-150mm) and steel pipe (32mm)Substrate: 2 x 13mm Plasterboard or concrete wall, min. 116mm thickMax FRR: -/120/120
System ID FC757
Service Penetration: DN 40mm steel pipeSubstrate: Concrete wall, min. 180mm thickMax FRR: -/360/360
System ID FC557
Service Penetration: Single cable and cable bundle (TPS and Cat6) up to 35mmSubstrate: 2 x 13mm Plasterboard or concrete wall, min. 116mm thickMax FRR: -/120/120
System ID FC521
Service Penetration: Cable tray with D1 or D2 cable configurationSubstrate: 2 x 13mm Plasterboard or concrete wall, min. 116mm thickMax FRR: -/120/120
System ID FC493
The FIRESTOP Inspection Hatch is a lightweight, cost effective inspection hatch for plasterboard walls or ceilings with some unique features. Size is 300x300mm with a pleasing powder-coated off-white finish.
System ID FC790
Service Penetration: 50mm Linear gapSubstrate: Concrete floor, min.120mm thickFRR: -/60/60
System ID FC520
AluTherm is a glasswool thermal wrap ideal for HVAC installations requiring thermal protection. Rolls are easy to handle and non-irritating. Size is 1200mm wide by 18m in length.
System ID FC808
Service: Protection of uninterrupted ducts:Rectangular: up to 1800mm × 1000mm (or equivalent area)Circular: up to 1000mm in diameterFire Source: Internal or external fireOrientation: Horizontal or verticalMax FRR: 120/120/120
System ID FC871
Service: Protection of uninterrupted three-sided ducts located close to a wall or floorFire Source: Internal or external fireOrientation: Horizontal or verticalMax FRR: 120/120/120
System ID FC872
Service: Protection of uninterrupted two-sided ducts located close to a cornerFire Source: Internal or external fireOrientation: Horizontal or verticalMax FRR: 120/120/120
System ID FC107
Service Penetration: Rectangular duct up to 1800mm x 1000mm or equivalent areaFire Source: Internal or external fireSubstrate: 1 x 13mm or 2 x 13mm Plasterboard wall, min. 90-142mm thick Max FRR: 120/120/120
System ID FC222
Service Penetration: Rectangular duct up to 1800mm x 1000mm or equivalent areaFire Source: Internal fire, one-way systemSubstrate: 1 x13mm or 2 x13 mm plasterboard wall, min. 90–142mm thickMax FRR: 120/120/120
System ID FC283
Service Penetration: Rectangular duct up to 1800mm x 1000mm or equivalent areaFire Source: External fire, one-way systemSubstrate: 1 x 13mm or 2 x 13mm Plasterboard wall, min. 90-142mm thickMax FRR: 120/120/120
System ID FC876
Service Penetration: Rectangular duct up to 1800mm x 1000mm or equivalent areaFire Source: Internal or external fireSubstrate: Concrete wall, min. 100mm thick, annular gap of up to 200mmMax FRR: 120/120/120
System ID FC229
Service Penetration: Rectangular duct up to 1800mm x 1000mm or equivalent areaFire Source: Internal fire, one-way systemSubstrate: Concrete wall, min. 90mm thickMax FRR: 120/120/120
System ID FC878
Service Penetration: Rectangular duct up to 1800mm x 1000mm or equivalent areaFire Source: Internal fire, one way sysemSubstrate: Concrete wall, min. 120mm thick, annular gap of 20–170mmMax FRR: 120/120/120
System ID FC502
Service Penetration: Rectangular duct up to 1800mm x 1000mm or equivalent areaFire Source: External fire, one-way systemSubstrate: Concrete wall, min. 90mm thickMax FRR: 120/120/120
System ID FC284
Service Penetration: Rectangular duct up to 1800mm x 1000mm or equivalent areaFire Source: Internal or external fireSubstrate: Concrete flat slab floor, min. 100mm thick, annular gap of up to 200mmMax FRR: 120/120/120
System ID FC223
Service Penetration: Rectangular duct up to 1800mm x 1000mm or equivalent areaFire Source: Internal fireSubstrate: Concrete flat slab floor, min. 120mm thick, annular gap of 20-170mmMax FRR: 120/120/120
System ID FC874
Service Penetration: Rectangular duct up to 1800mm x 1000mm or equivalent areaFire Source: External fireSubstrate: Concrete flat slab floor, min. 100mm thick, annular gap of up to 200mmMax FRR: 120/120/120
System ID FC285
Service Penetration: Rectangular duct up to 1800mm x 1000mm or equivalent areaFire Source: Internal or external fireSubstrate: 16mm Plasterboard ceiling structure, min. 125mm thickMax FRR: 60/60/60
System ID FC227
Service Penetration: Rectangular duct up to 1800mm x 1000mm or equivalent areaFire Source: Internal fireSubstrate: 16mm Plasterboard ceiling structure, min. 125mm thickMax FRR: 60/60/60
System ID FC305
Service Penetration: Rectangular duct up to 1800mm x 1000mm or equivalent areaFire Source: External fireSubstrate: 16mm Plasterboard ceiling structure, min. 125mm thickMax FRR: 60/60/60
System ID FC546
Service Penetration: Circular duct up to 1000mm diameterFire Source: Internal or external fire Substrate: 1 x 13mm or 2 x 13mm Plasterboard wall, min. 90-142mm thick Max FRR: 120/120/120
System ID FC726
Service Penetration: Circular duct up to 1000mm diameterFire Source: Internal fire, one-way systemSubstrate: 1 x 13mm or 2 x 13mm Plasterboard wall, min. 90-142mm thickMax FRR: 120/120/120
System ID FC350
Service Penetration: Circular duct up to 1000mm diameterFire Source: External fire, one-way systemSubstrate: 1 x 13mm or 2 x 13mm Plasterboard wall, min. 90-142mm thickMax FRR: 120/120/90
System ID FC560
Service Penetration: Circular duct up to 1000mm diameterFire Source: Internal fire, one-way systemSubstrate: Concrete wall, min. 100mm thickMax FRR: 120/120/90
System ID FC232
Service Penetration: Circular duct up to 1000mm diameterFire Source: Internal fire, one-way systemSubstrate: Concrete wall, min. 100mm thickMax FRR: 120/120/120
System ID FC718
Service Penetration: Circular duct up to 1000mm diameterFire Source: Internal fire, one-way systemSubstrate: Concrete wall, min. 120mm thick, oversized rectangular or square aperture Max FRR: 120/120/120
System ID FC556
Service Penetration: Circular duct up to 1000mm diameterFire Source: External fire, one-way systemSubstrate: Concrete wall, min. 100mm thickMax FRR: 120/120/90
System ID FC877
Service Penetration: Circular duct up to 1000mm diameterFire Source: Internal or exernal fireSubstrate: Concrete wall, min. 100mm thick, oversized rectangular or square apertureMax FRR: 120/120/90
System ID FC716
Service Penetration: Circular duct up to 1000mm diameterFire Source: Internal or external fireSubstrate: Concrete flat slab floor, min. 100mm thickMax FRR: 120/120/90
System ID FC719
Service Penetration: Circular duct up to 1000mm diameterFire Source: Internal fireSubstrate: Concrete flat slab floor, min. 100mm thickMax FRR: 120/120/120
System ID FC720
Service Penetration: Circular duct up to 1000mm diameterFire Source: External fireSubstrate: Concrete flat slab floor, min. 100mm thickMax FRR: 120/120/90
System ID FC715
Service Penetration: Circular duct up to 1000mm diameterFire Source: Internal or external fireSubstrate: Concrete flat slab floor, min. 100mm thick, oversized rectangular or square apertureMax FRR: 120/120/90
System ID FC503
Service Penetration: Circular duct up to 1000mm diameterFire Source: Internal fireSubstrate: Concrete flat slab floor, min. 120mm thick, oversized rectangular or square apertureMax FRR: 120/120/120
System ID FC717
Service Penetration: Circular duct up to 1000mm diameterFire Source: External fireSubstrate: Concrete flat slab floor, min. 100mm thick, oversized rectangular or square apertureMax FRR: 120/120/90
System ID FC307
Service Penetration: Circular duct up to 1000mm diameterFire Source: Internal or external fireSubstrate: 16mm Plasterboard ceiling structure, min. 125mm thickMax FRR: 60/60/60
System ID FC294
Service Penetration: Circular duct up to 1000mm diameterFire Source: Internal fireSubstrate: 16mm Plasterboard ceiling structure, min. 125mm thickMax FRR: 60/60/60
System ID FC410
Service Penetration: Circular duct up to 1000mm diameterFire Source: External fireSubstrate: 16mm Plasterboard ceiling structure, min. 125mm thickMax FRR: 60/60/60
System ID FC809
Service Penetration: Duct support channels, cables and sprinkler pipesFire Source: Internal or external fireFire Barrier: Rectangular or circular duct wrapped with FIRESTOP Duct Wrap-38Max FRR: -/120/120
System ID FC401
Service Penetration: Circular duct up to 300mm diameterFire Source: Internal fireSubstrate: 1 x 13mm Plasterboard on concrete wall, min. 90 thickMax FRR: 120/120/60
System ID FC542
Service Penetration: Circular duct up to 300mm diameterFire Source: Internal fire, one-way systemSubstrate: 1 x 13mm Plasterboard on concrete wall, min. 90 thickMax FRR: 120/120/60
System ID FC224
Service Penetration: Circular duct up to 300mm diameterFire Source: Internal fireSubstrate: Composite (min. 60mm topping) or concrete flat slab floor, min. 120mm thickMax FRR: 120/120/30
System ID FC804
Service Penetration: Duct access hatchFire Source: Internal or external fireFire Barrier: Rectangular duct wrapped with FIRESTOP Duct Wrap-38Orientation: Horizontal or verticalMax FRR: -/120/120
System ID FC805
Service Penetration: Duct access hatchFire Source: Internal or external fireFire Barrier: Circular duct wrapped with FIRESTOP Duct Wrap-38Orientation: Horizontal or verticalMax FRR: -/120/120
System ID FC545
Stainless steel ties for securing duct or thermal wrap in HVAC installations. Easy-clip design provides strong joins without heavy metal banding.
System ID FC875
FIRESTOP Weld Pins secure FIRESTOP Duct Wrap-38, FIRESTOP Duct Wrap-25, or other thermal wraps to sheet metal ducts of any shape (circular, rectangular, or square).
System ID FC727
FIRESTOP Embossed Tape is a high-performance, multi-layered, fire-rated polyester and aluminium foil tape with cold-weather adhesive. Durable, UV- and fungi-resistant, it withstands extreme conditions. Ideal for FIRESTOP Duct Wrap-38/25, vapour barriers, and general insulation applications.
System ID FC537
Timber systems are currently being assessed to AS1530.4 and will be displayed here when complete. For a summary of what is currently available under EN1366 tests download the Protecta Timber Systems Handbook opposite.
System ID FC732
Service Penetration: Plastic pipe (PVC, PVC with socket, PVC Stormwater, HDPE, PP-R, PP-MD, PEX, PB & PEX/Al/PEX) up to 225mm Substrate: Concrete flat slab, min. 70mm thickMax FRR: -/240/240
System ID FC777
Service Penetration: Plastic (PVC, HDPE & PP-R) pipe up to 150mmSubstrate: Concrete wall, min. 150mm thickMax FRR: -/180/180
System ID FC629
Service Penetration: PVC and HDPE floor waste (FWG) up to 100mm Substrate: Concrete flat slab, min. 70mm thick Max FRR: -/180/120
System ID FC690
Service Penetration: Plastic pipe (PVC, PEX, PB, PEX/AL/PE &PP-R) up to 100mm Substrate: Rib and timber infill, min. 70mm concrete topping thicknessMax FRR: -/120/120
System ID FC734
Service Penetration: PVC floor waste (FWG) 80 and 100mmSubstrate: Rib and timber infill, min. 70mm concrete topping thicknessMax FRR: -/120/120
System ID FC730
Service Penetration: Plastic Pipe (PVC, HDPE, PEX, PP-R & PP-MD) up to 160mmSubstrate: Hollow core concrete floor, min. 150mm thickMax FRR: -/90/90
System ID FC731
Service Penetration: PVC plastic floor waste (FWG) 80 and 100mm Substrate: Hollow core concrete floor, min. 150mm thickMax FRR: -/90/90
System ID FC501
Service Penetration: 32mm Copper pipe with 19mm thick NBR insulation Substrate: Concrete flat slab, min. 150mm thickMax FRR: -/120/90
System ID FC221
Service Penetration: PVC (up to 100mm) and PEX (up to 25mm) pipes through a Substrate: CLT floor, min 105 thickMax FRR: -/60/60
System ID FC220
Service Penetration: Plastic pipe (PVC, PP-R or PEX) up to 100mmSubstrate: Composite floor (flat profile), min 70mm thick concrete toppingMax FRR: -/120/120
System ID FC631
Service Penetration: Electric cables (TPS, Cat6 & Mains) or A/C mixed servicesSubstrate: 2 x 13mm Plasterboard ceiling structure, min. 235mm thickMax FRR: -/90/90
System ID FC499
Service Penetration: Electric cables (TPS & Cat6)Substrate: 1 x 16mm Plasterboard ceiling structure, min. 225mm thickMax FRR: -/60/60
System ID FC735
Service Penetration: Plastic pipe (PVC, PVC with socket, PP-R, PEX & PB) up to 150mmSubstrate: 2 x13mm Plasterboard ceiling structure, min. 235mm thick Max FRR: -/90/90
System ID FC740
Service Penetration: Plastic pipe (PVC up to 100mm and PEX up to 25mm) Substrate: 1 x 16mm Plasterboard ceiling structure, min. 225mm thickMax FRR: -/60/60
System ID FC736
Service Penetration: PVC floor waste (80mm or 100mm) Substrate: 2 x 13mm or 1 x 16mm Plasterboard ceiling structure, min. 225-235mm thickMax FRR: -/90/60
System ID FC737
Service Penetration: Plastic pipe (PVC, PB, PEX, PP-MD, PE-RT/AL/PE-RT, PP-R, PEX/AL/PEX & PEX/AL/PE) up to 225mmSubstrate: 1 x 13mm Plasterboard or concrete wall, min. 90mm thickMax FRR: -/60/60
System ID FC522
Service Penetration: Plastic pipe (PVC, PEX, HDPE, PP-R) up to 150mmSubstrate: 1 x 16mm or 1 x 19mm Plasterboard or concrete wall, min. 96-130mm thickMax FRR: -/120/120
System ID FC523
Service Penetration: Plastic pipes (PVC, PEX, PB, PP-R) up to 100mmSubstrate: 1 x 13mm Standard plasterboard or concrete wall, min. 90-118mm thickMax FRR: -/30/30
System ID FC738
Service penetration: Plastic pipes (PVC, PP-R, PB, PEX & PEX/AL/PE) up to 100mm Substrate: 1 x 13mm (STD or FR), 16mm, or 19mm plasterboard or concrete wall, min. 90 - 130mm thick Max FRR: -/120/90
System ID FC742
Service Penetration: Plastic pipes (PVC, PEX, PEX/AL/PEX) up to 100mmService Penetration: 2 x 13mm or 2 x 16mm plasterboard or concrete wall, min. 116-128mm thickMax FRR: -/120/120
System ID FC632
Service Penetration: Cables (TPS, Cat6, Fire Alarm & Mains) in bundles up to 60 cables and 25mm PVC conduitSubstrate: 1 x 13mm Plasterboard or concrete wall, min. 90mm thickMax FRR: -/60/60
System ID FC494
Service Penetration: A/C Mixed Services (up to 3 x pair coils with cables and pipe) Substrate: 1 x 13mm Plasterboard or concrete wall, min. 90mm thickMax FRR: -/60/60
System ID FC293
Service Penetration: Electric cables (TPS, Cat6 & Mains)Substrate: CLT Floor, min. 110mm thickMax FRR: -/60/60
System ID FC633
Service Penetration: A/C mixed services (pair coil, TPS cable & flexi hose)Substrate: 1 x 13mm Plasterboard or concrete wall, min. 90mm thickMax FRR: -/60/60
System ID FC750
Service Penetration: Plastic pipe (PVC up to 15mm & HDPE up to 110mm)Substrate: Speedpanel wall, min. 78mm thickMax FRR: -/120/120
System ID FC775
Service Penetration: PVC (up to 65mm) and PEX (up to 25mm) pipesSubstrate: CLT wall, min. 110mm thick Max FRR: -/60/60
System ID FC752
Service Penetration: Plastic pipe (PVC, PEX, PEX/AL/PEX) up to 100mmSubstrate: 75mm Hebel Powerpanel with 13mm plasterboard pattress Max FRR: -/120/120
System ID FC771
Service Penetration: Electric cables (TPS, Cat6, Fire alarm, Optic fibre and Mains) or A/C mixed servicesSubstrate: Rib and timber infill, min. 70mm concrete topping thicknessMax FRR: -/90/90
System ID FC772
Service Penetration: Electric cables (TPS, Cat6, Fire alarm, Fibre optic & Mains) or A/C mixed servicesSubstrate: CLT floor, min. 105mm thickMax FRR: -/60/60
System ID FC773
Service Penetration: Electric cables (TPS, Cat6, Fire alarm, Fibre optic & Mains)Substrate: Concrete flat slab, min 70mm thickMax FRR: -/60/60
System ID FC524
Service Penetration: 100mm PVC floor waste (FWG)Substrate: CLT floor, min.105mm thickMax FRR: -/60/-
System ID FC634
Service Penetration: PVC pipe (40, 50 & 100mm)Substrate: 2 x 13mm Plasterboard ceiling structure, min. 235mm thickMax FRR: -/90/90
System ID FC639
Service Penetration: Plastic pipes (PVC, HDPE, PP-R, PP-M, PEX, PB & PEX/AL?PESubstrate: Concrete flat slab, min. 70mm thickMax FRR: -/120/120
System ID FC534
Service Penetration: PVC (25-100mm) or PEX (15-32mm) pipeSubstrate: CLT floor, min. 110mm thickMax FRR: -/60/60
System ID FC635
Service Penetration: PVC floor waste (FWG) 80 and 100mmSubstrate: Concrete flat slab, min. 70mm thickMax FRR: -/120/120
System ID FC554
Service Penetration: PVC floor waste (50-100mm)Substrate: CLT floor, min. 110mm thickMax FRR: -/60/60
System ID FC688
Service Penetration: Plastic pipe (PVC, HDPE, PP-MD, PP-R, PEX, PB or PEX/AL/PE) up to 150mmSubstrate: Composite floor, min. 70mm thick concrete toppingMax FRR: -/120/120
System ID FC687
Service Penetration: PVC or HDPE floor waste (FWG) up to 100mmSubstrate: Composite floor, min. 70mm thick concrete toppingMax FRR: -/120/120
System ID FC770
Service Penetration: Electric cables and A/C mixed servicesSubstrate: Composite floor, min. 70mm thick concrete toppingMax FRR: -/120/90
System ID FC498
Service Penetration: Electric cable (TPS, Cat6 & Mains)Substrate: CLT floor, min. 110mm thickMax FRR: -/60/60
System ID FC671
Service Penetration: Plastic pipe (PVC, HDPE, PP-R or PP-MD) up to 150mmSubstrate: Concrete flat slab, min. 120mm thickMax FRR: -/180/180
System ID FC776
Service Penetration: Plastic pipe (PVC, HDPE & PP-R) up to 150mmSubstrate: Concrete wall, min. 150mm thickMax FRR: -/180/180
System ID FC525
Service Penetration: PVC floor waste (FWG) 80mmSubstrate: Concrete flat slab, min. 150mm thickMax FRR: -/90/90
System ID FC630
Service Penetration: Metal electric flush box (single, double or back-to-back)Substrate: 1 x 13mm (STD or FR) or 19mm plasterboard wall, min. 90mm thickMax FRR: -/120/90
System ID FC691
Service Penetration: 15mm Brass wingbackSubstrate: 1 x 13mm Plasterboard wall, min. 90mm thickMax FRR: -/60/60
System ID FC865
Service Penetration: PEX pipe, 16-40mmSubstrate: 2 x 13mm Plasterboard wall or concrete wall, min. 116mm thickMax FRR: -/120/120
System ID FC887
Service Penetration: PEX pipe, 16-32mmSubstrate: 1 x 13mm Plasterboard wall or concrete wall, min 116mm thickMax FRR: -/60/60
System ID FC864
Service Penetration: PEX-AL-PEX pipe, 16-32mmSubstrate: 2 x 13mm Plasterboard wall or concrete wall, min, 116mm thick Max FRR: -/120/120
System ID FC855
Service Penetration: PEX-AL-PEX pipe, 16-32mmSubstrate: 1 x 13mm Plasterboard wall or concrete wall, min 90mm thickMax FRR: -/60/60
System ID FC435
Service Penetration: Polybutylene (PB) pipe, 15-28mm Substrate: 2 x 13mm Plasterboard wall or concrete wall, min 116mm thickMax FRR: -/120/120
System ID FC885
Service Penetration: Mixed pair coil services - FR pair coil with or without TPS cable and PVC pipe Substrate: 2 x 13mm Plasterboard wall or concrete wall, min.116mm thick Max FRR: -/120/120
System ID FC889
Service Penetration: Mixed pair coil services - FR pair coil with or without TPS cable and PVC pipe Substrate: 1 x 13mm Plasterboard wall or concrete wall, min. 90mm thick or greaterMax FRR: -/60/60
System ID FC886
Service Penetration: PE pair coilSubstrate: 2 x 13mm Plasterboard wall or concrete wall, min. 116mm thick Max FRR: -/120/60
System ID FC888
Service Penetration: PE Pair CoilSubstrate: 1 x 13mm Plasterboard wall or concrete wall, min. 90mm thick Max FRR: -/60/45
System ID FC862
Joints, vertical or horizontal, up to 40mm wide in plasterboard (1 x 13mm) or concrete (min 90mm) walls. AGNI-Seal to both faces of the wall. Max FRR -/60/60.
System ID FC836
Joints, vertical or horizontal, up to 40mm wide in plasterboard (2 x 13mm) or concrete (min 116mm) walls. AGNI-Seal to both faces of the wall. Max FRR -/120/120.
System ID FC834
Joints in concrete floors (min 120mm) from 10mm to 40mm wide. AGNI-Seal to both faces of floor. Max FRR -/180/150.
System ID FC820
Copper pipe (any size up to 100mm) through a 1 x 13mm or greater plasterboard ceiling. AGNI-Seal to the depth of the plasterboard. Max FRR -/60/60.
System ID FC821
Steel pipe (up to 50mm) through a 1 x 13mm or greater plasterboard ceiling. AGNI-Seal to the depth of the plasterboard. Max FRR -/60/60.
System ID FC822
Sprinkler head and steel pipe through a 1 x 13mm or greater plasterboard ceiling. AGNI-Seal to the depth of the plasterboard. Max FRR -/60/60.
System ID FC823
Single cables (TPS, Coax or Data, 40mm spacing) through a 1 x 13mm or greater plasterboard ceiling. AGNI-Seal to the depth of the plasterboard. Max FRR -/60/60.
System ID FC846
Single cables (Data, Coax, TPS) through one side only of a 1 x 13mm plasterboard wall. Spacing 40mm. AGNI-Seal to the depth of the wall with 10mm cone. Max FRR -/60/60.
System ID FC853
Single cable up to 21mm OD through a 1 x 13mm plasterboard wall or 118mm concrete wall. AGNI-Seal to the depth of the wall with 20mm cone. Max FRR -/60/60.
System ID FC847
Cable bundle (up to 5 x data cables) through one side only of a 1 x 13mm plasterboard wall. AGNI-Seal to the depth of the wall with 20mm cone. Max FRR -/60/60.
System ID FC848
Cable bundle (up to 5 x TPS cables) through one side only of a 1 x 13mm plasterboard wall. AGNI-Seal to the depth of the wall with 20mm cone. Max FRR -/60/60.
System ID FC890
Single aluminium core cable (25mm - 52mm) through 1 x 13mm plasterboard wall or concrete wall 90mm or greater. AGNI-Seal to the depth of the wall with 30mm cone. Max FRR -/60/60.
System ID FC247
Copper pipe (32mm - 150mm) through a 1 x 13mm plasterboard wall or concrete wall (90mm or greater). AGNI-Seal cone of 30mm each side of wall. Max FRR -/60/-.
System ID FC849
Brass Wingback through fire-side only of a 1 x 13mm plasterboard wall. AGNI-Seal to the depth of the wall with 20mm cone. Max FRR -/60/60.
System ID FC891
Threaded steel rod (12mm) through 1 x 13mm plasterboard wall or concrete wall 90mm or greater. AGNI-Seal to the depth of the wall with 20mm cone both sides of wall. Max FRR -/60/60.
System ID FC535
Cables (up to 8 x TPS power cables) through a 2 x 13mm plasterboard wall or concrete wall (116mm or greater). AGNI-Seal in annular space and 30mm cone each side of wall. Max FRR -/120/120.
System ID FC830
Cables (up to 13 x CAT5 data cables) through a 2 x 13mm plasterboard wall or concrete wall (116mm or greater). AGNI-Seal in annular space and 30mm cone each side of wall. Max FRR -/120/120.
System ID FC540
Fibre Optic Cable (9.6mm) through a 2 x 13mm plasterboard wall or concrete wall (116mm or greater). AGNI-Seal in annular space to the depth of the plasterboard (26mm) and 20mm cone each side of wall. Max FRR -/120/120
System ID FC852
Copper or steel pipe (10mm - 100mm) through a 2 x 13mm plasterboard wall or concrete wall (116mm or greater). AGNI-Seal each side of wall with AGNI-Shield wrap. Max FRR -/120/120.
System ID FC616
Bare copper or steel pipes up to 150mm through a 120mm concrete floor/ceiling. AGNI-Seal to one or both sides, with AGNI-Shield wrap. Max FRR -/120/120
System ID FC841
Cable bundles (up to 8 x TPS cables) through a 100mm CLT wall. AGNI-Seal to the depth of the wall with 10mm cone each side. Max FRR -/60/60.
System ID FC304
Cable bundle (up to 8 x TPS cables) through a Hebel wall (75mm or greater). AGNI-Seal to the depth of the wall with 30mm cone each side. Max FRR -/120/60.
System ID FC217
Cable bundle (up to 8 x TPS cables) through a Shaftwall (25mm Shaftliner and 16mm FR plasterboard). AGNI-Seal to depth of wall with a 30mm cone fillet each side. Max FRR -/60/60
System ID FC459
Cables (power, data and alarm) fibre optic 4.8mm) through a Shaftwall (25mm Shaftliner and 16mm FR plasterboard). Cable types to have 20mm separation. AGNI-Seal to depth of wall. Max FRR -/60/60
System ID FC168
Cable (fibre optic 4.8mm) through a Shaftwall (25mm Shaftliner and 16mm FR plasterboard). AGNI-Seal to depth of wall. Max FRR -/60/60
System ID FC455
Alarm cable bundle (up to 8 cables) through a Shaftwall (25mm Shaftliner and 16mm FR plasterboard). AGNI-Seal to depth of wall with a 10mm cone fillet each side. Wrap with 50mm AGNI-Shield. Max FRR -/60/60
System ID FC894
Copper or steel pipe (32mm - 100mm) through a Hebel wall (75mm or greater). AGNI-Seal to depth of wall with AGNI-Shield wrap. Max FRR -/120/120.
System ID FC231
Copper or steel pipe (32mm - 100mm) through a Shaftwall (25mm Shaftliner and 16mm FR plasterboard). AGNI-Seal to depth of wall with AGNI-Shield wrap. Max FRR -/60/60.
System ID FC462
Steel pipe 60mm with alarm cable through a Shaftwall (25mm Shaftliner and 16mm FR plasterboard). AGNI-Seal to depth of wall. Max FRR -/60/15
System ID FC460
Copper pipe (bare - 100mm) through a Shaftwall (25mm Shaftliner and 16mm FR plasterboard). AGNI-Seal to depth of wall. Max FRR -/60/-
System ID FC640
Cable (copper 20mm) through a Hebel wall (75mm or greater). AGNI-Seal to depth of wall with a 30mm cone fillet each side. Max FRR -/120/60.
System ID FC216
Cable (copper 20mm) through a Shaftwall (25mm Shaftliner and 16mm FR plasterboard). AGNI-Seal to depth of wall with a 30mm cone fillet each side. Max FRR -/60/15
System ID FC456
Cable (Copper Core 25mm) through a Shaftwall (25mm Shaftliner and 16mm FR plasterboard). AGNI-Seal to depth of wall with a 10mm cone each side. AGNI-Shield 50mm wide to each side. Max FRR -/60/60
System ID FC282
Cable (aluminium 25mm) through a Hebel wall (75mm or greater). AGNI-Seal to depth of wall with a 30mm cone fillet each side. Max FRR -/120/120
System ID FC230
Cable (aluminium 25mm) through a Shaftwall (25mm Shaftliner and 16mm FR plasterboard). AGNI-Seal to depth of wall with a 30mm cone fillet each side. Max FRR -/60/60
System ID FC454
Cable (Aluminium Core 30mm) through a Shaftwall (25mm Shaftliner and 16mm FR plasterboard). AGNI-Seal to depth of wall with a 10mm cone each side. AGNI-Shield 50mm wide to each side. Max FRR -/60/60
System ID FC806
Plastic pipe (PVC-U, 32-150mm) through a concrete or AAC floor or ceiling (100mm or greater). Single AGNI-Sleeve top fixed with tabs and 10mm AGNI-Seal sealant at top of floor/ceiling. Max FRR -/120/120.
System ID FC857
Plastic pipe (PVC-U, up to 100mm) through a concrete or AAC floor or ceiling (190mm or greater). Single AGNI-Sleeve with tabs top fixed with 10mm AGNI-Seal sealant at top of floor/ceiling. Max FRR -/360/360.
System ID FC867
Plastic pipe (PVC-U, up to 100mm diam) through a composite floor (topping min 70mm). Single AGNI-Sleeve top fixed with 10mm AGNI-Seal at top of floor. Max FRR -/60/60.
System ID FC880
Plastic pipe (PVC-U, 32-100mm diam) through a composite floor (topping min 70mm). Single AGNI-Sleeve bottom fixed with 20mm AGNI-Board at top of floor. Max FRR -/60/60.
System ID FC813
Aquatherm plastic pipe (PPR, 32-90mm) through a concrete or AAC floor/ceiling (100mm or greater). Single AGNI-Sleeve top fixed with tabs with 10mm AGNI-Seal sealant to top of floor/ceiling. Max FRR -/120/120.
System ID FC858
Aquatherm plastic pipe (PPR, 125mm) through a concrete or AAC floor/ceiling (190mm or greater). Double layer AGNI-Sleeve with tabs top fixed with 10mm AGNI-Seal sealant to top of floor/ceiling. Max FRR -/360/360.
System ID FC868
Aquatherm plastic pipe (PP-R, 90mm) through a composite floor (topping min 70mm). Single AGNI-Sleeve top fixed with 10mm AGNI-Seal sealant to top of floor. Max FRR -/120/120.
System ID FC881
Aquatherm plastic pipe (PP-R, 90mm) through a composite floor (topping min 70mm). Single AGNI-Sleeve bottom fixed with 20mm AGNI-Board to top of floor. Max FRR -/60/60.
System ID FC870
Flexible Conduit 50mm, empty or with up to 6 x TPS cables through a composite floor (topping min 70mm). Single AGNI-Sleeve with tabs top fixed with 10mm AGNI-Seal sealant to top of floor. Max FRR -/120/120.
System ID FC879
Flexible Conduit 50mm, empty or with TPS cables through a composite floor (topping min 70mm). Single AGNI-Sleeve with tabs bottom fixed with 20mm AGNI-Board to top of floor. Max FRR -/60/60.
System ID FC869
Pair Coil with condensate pipe and TPS cable through a composite floor (topping min 70mm). Single AGNI-Sleeve with tabs top fixed with 10mm AGNI-Seal sealant to top of floor. Max FRR -/120/90.
System ID FC814
Plastic pipe (PVC-U, 32-100mm) through a concrete or AAC floor/ceiling (120mm or greater). Single AGNI-Sleeve bottom fixed with 20mm AGNI-Seal sealant to bottom of floor/ceiling. Max FRR -/120/120.
System ID FC815
Aquatherm plastic pipe (PPR, 40-90mm) through a concrete or AAC floor/ceiling (120mm or greater). Single AGNI-Sleeve bottom fixed with 20mm AGNI-Seal sealant to bottom of floor/ceiling. Max FRR -/120/120.
System ID FC859
Floor waste (80mm with PVC elbow) through a concrete or AAC floor/ceiling (190mm or greater). Single layer AGNI-Sleeve with tabs and ceramic backing. Max FRR -/360/360.
System ID FC816
Plastic pipe (PVC-U, 80-100mm) through a 1 x 13mm plasterboard wall or concrete wall (116mm or greater). Single AGNI-Sleeve extending 25mm from each side of wall with AGNI-Seal sealant. Max FRR -/60/60.
System ID FC827
PEX pipe (40mm) through a 1 x 13mm plasterboard wall or concrete wall (116mm or greater). Single AGNI-Sleeve extending 25mm from each side of wall with AGNI-Seal sealant. Max FRR -/60/60.
System ID FC854
Kelox Pipe (PERT-AL-PERT) with PE Foam insulation up to 13mm thick through a 1 x 13mm plasterboard wall or concrete wall (118mm or greater). Single AGNI-Sleeve extending 10mm from each side of wall with AGNI-Seal sealant. Max FRR -/60/45.
System ID FC361
Service Penetration: Copper Pipe 15-50mm with nitrile rubber insulation 9-38mm thickSubstrate: 2 x 13mm Plasterboard wall or concrete wall, min. 116mm thickMax FRR: -/120/120
System ID FC288
Service Penetration: 2 x Copper pipes (32mm & 15mm) with 32mm & 25mm nitrile rubber insulationSubstrate: 2 x 13mm Plasterboard wall or concrete wall, min. 116mm thickMax FRR: -/120/120
System ID FC362
Service Penetration: 3 x Copper Pipes (15mm, 32mm & 50mm) with 32mm & 25mm nitrile rubber insulationSubstrate: 2 x 13mm Plasterboard wall or concrete wall, min. 116mm thickMax FRR: -/120/120
System ID FC609
Pair Coils (single or double set of pair coils with TPS cables, PE or FR insulation) through a 2 x 13mm plasterboard wall or concrete wall (116mm or greater). Single AGNI-Sleeve extending 25mm from each side of wall with AGNI-Straps and AGNI-Seal. Max FRR -/120/60.
System ID FC551
Service Penetration: PEX Pipe 16-32mm with nitrile rubber insulation 9-38mm thickSubstrate: 2 x 13mm Plasterboard wall or concrete wall, min. 116mm thick Max FRR: -/120/120
System ID FC844
PVC-U pipe (32mm - 80mm) through a 100mm CLT wall. Single AGNI-Sleeve extending 10mm from each side of wall with AGNI-Seal sealant. Max FRR -/60/60.
System ID FC843
PEX pipe (16mm - 25mm) through a 100mm CLT wall. Single AGNI-Sleeve extending 10mm from each side of wall with AGNI-Seal sealant. Max FRR -/60/60.
System ID FC845
Flexible Conduit (25mm) through a 100mm CLT wall. Single AGNI-Sleeve extending 10mm from each side of wall with AGNI-Seal sealant. Max FRR -/60/60.
System ID FC496
TPS Cable bundle through a 1x13mm + 1x16mm plasterboard ceiling. AGNI-Sleeve/AGNI-Shield wrap with AGNI-Seal. Incipient Fire Rating 60min. Max FRR -/60/60
System ID FC497
Alarm Cable bundle through a 1x13mm + 1x16mm plasterboard ceiling. AGNI-Sleeve/AGNI-Shield wrap with AGNI-Seal. Incipient Fire Rating 60min. Max FRR -/60/60
System ID FC505
Data Cable bundle through a 1x13mm + 1x16mm plasterboard ceiling. AGNI-Sleeve/AGNI-Shield wrap with AGNI-Seal. Incipient Fire Rating 60min. Max FRR -/60/60
System ID FC511
Conduit (25mm PVC) empty or filled with up to 8 fibre optic cables, through a 1x13mm + 1x16mm plasterboard ceiling. AGNI-Sleeve/AGNI-Shield wrap with AGNI-Seal. Incipient Fire Rating 60min. Max FRR -/60/60
System ID FC555
Copper or steel pipe 25mm-100mm through a 1x13mm + 1x16mm plasterboard ceiling. AGNI-Sleeve/AGNI-Shield wrap with AGNI-Seal. Incipient Fire Rating 60min. Max FRR -/60/45
System ID FC817
Plastic pipe (PVC-U, 40-100mm) through a 1 x 13mm plasterboard wall or concrete wall (116mm or greater). AGNI-Wrap 50mm extending 25mm from each side of wall with AGNI-Seal sealant. Max FRR -/60/60.
System ID FC818
Plastic pipe (PEX, 16-25mm) through a 1 x 13mm plasterboard wall or concrete wall (116mm or greater). AGNI-Wrap 50mm extending 25mm from each side of wall with AGNI-Seal sealant. Max FRR -/60/60.
System ID FC850
PEX pipe (up to 25mm) through a 1 x 13mm plasterboard wall or masonry wall (90mm or greater). Fire side only. AGNI-Wrap 50mm extending 25mm from the wall. No sealant required. Max FRR -/60/60.
System ID FC828
Flexible conduit (25mm) with TPS cables through a 1 x 13mm plasterboard wall or concrete wall (116mm or greater). AGNI-Wrap 50mm extending 25mm from each side of wall with AGNI-Seal sealant. Max FRR -/60/60.
System ID FC448
Service Penetration: 25mm PVC Conduit empty or filled with up to 8 fibre optic cablesSubstrate: 2 x 13mm Plasterboard wall or concrete wall, min. 116mmMax FRR: -/120/120
System ID FC451
Service Penetration: 25mm Flexible Conduit empty or filled with up to 8 fibre optic cablesSubstrate: 2 x 13mm Plasterboard wall or concrete wall, min. 116mm thick Max FRR: -/120/120
System ID FC832
Plastic pipe (PVC-U, 20mm) through a 2 x 13mm plasterboard wall or concrete wall (116mm or greater). AGNI-Wrap single layer each side of wall with AGNI-Seal sealant. Max FRR -/120/120.
System ID FC856
Plastic pipe (PVC-U 32mm up to 100mm) through a 2 x 13mm plasterboard wall or concrete wall (116mm or greater). AGNI-Wrap single or double layer each side of wall with AGNI-Seal sealant. Max FRR -/120/120.
System ID FC863
PEX pipe (16-40mm) through a 2 x 13mm plasterboard wall or concrete wall (116mm or greater). AGNI-Wrap single layer each side of wall with AGNI-Seal sealant. Max FRR -/120/120.
System ID FC829
Plastic pipe (Blue PE, 20mm, 63mm) through a 2 x 13mm plasterboard wall or concrete wall (116mm or greater). AGNI-Wrap (single or double layer) each side of wall with AGNI-Seal sealant. Max FRR -/120/120.
System ID FC831
Service Penetration: 25mm PEX pipeSubstrate: Hebel wall, min. 75mm thickMax FRR: -/120/120
System ID FC452
Service Penetration: PEX pipe 16-20mmSubstrate: Shaftwall - 25mm Shaftliner and 16mm FR plasterboardMax FRR: -/60/60
System ID FC218
PEX pipe (25mm) through a Shaftwall (25mm Shaftliner and 16mm FR plasterboard). AGNI-Wrap 50 single layer each side of wall with AGNI-Black sealant. Max FRR -/60/60.
System ID FC453
Conduit (PVC, 25mm, empty or filled with data, alarm, fibre optic cables) through a Shaftwall (25mm Shaftliner and 16mm FR plasterboard). AGNI-Wrap 50 single layer each side of wall with AGNI-Black sealant. Max FRR -/60/60
System ID FC833
Pair Coil with cable and pipe through a Hebel wall (75mm or greater). AGNI-Wrap single layer each side of wall with AGNI-Black sealant. Max FRR -/120/120.
System ID FC219
Pair Coil with cable and pipe through a Shaftwall (25mm Shaftliner and 16mm FR plasterboard). AGNI-Wrap single layer each side of wall with AGNI-Black sealant. Max FRR -/60/60.
System ID FC851
Flexible Conduit (50mm) filled with up to 9 TPS cables through a 2 x 13mm plasterboard wall or concrete wall (116mm or greater). AGNI-Wrap single layer each side of wall with AGNI-Seal sealant. Max FRR -/120/120.
System ID FC225
PVC-U Conduit (up to 50mm) empty or filled with up to 14 TPS cables through a 2 x 13mm plasterboard wall or concrete wall (116mm or greater). AGNI-Wrap 25 single layer each side of wall with AGNI-Seal sealant. Max FRR -/120/120.
System ID FC892
Pair Coils, single or double, PE insulation with TPS cable through a 1 x 13mm plasterboard wall or concrete wall (90mm or greater). AGNI-Wrap in aperture with AGNI-Black sealant between wrap and coils. Finish with AGNI-Seal fillet over exposed AGNI-Wrap. Max FRR -/60/60.
System ID FC860
Floor Waste (40mm) through a concrete floor/ceiling (120mm or greater). AGNI-Wrap-25 single layer within the annular space and double layer beneath No sealant required. Max FRR -/240/240.
System ID FC861
Floor Waste (up to 80mm) through a concrete floor/ceiling (120mm or greater). AGNI-Wrap-25 double layer within the annular space and double layer beneath No sealant required. Max FRR -/120/120.
System ID FC842
Flexible conduit, 25mm, empty or with up to 3 TPS cables through a 1 x 16mm or greater plasterboard ceiling. AGNI-Wrap around conduit with AGNI-Seal. Max FRR -/60/60.
System ID FC835
Flexible conduit, 50mm, empty or with up to 6 TPS cables through a 1 x 16mm or greater plasterboard ceiling. AGNI-Wrap around conduit with AGNI-Seal. Max FRR -/60/60.
System ID FC824
Pair Coils with PE or FR insulation, up to 3 sets, through a 1 x 13mm or greater plasterboard ceiling. AGNI-Wrap around each pair coil and the bundle. Max FRR -/60/60.
System ID FC839
PVC-U pipe (40mm - 80mm) through a 1 x 16mm or greater plasterboard ceiling. AGNI-Wrap around pipe with AGNI-Seal. Max FRR -/60/60.
System ID FC837
100mm PVC-U pipe through a 1 x 16mm or greater plasterboard ceiling. AGNI-Wrap (one or two layers) around pipe with AGNI-Seal. Max FRR -/60/60.
System ID FC838
PEX pipe (16mm - 40mm) through a 1 x 16mm or greater plasterboard ceiling. AGNI-Wrap round pipe with AGNI-Seal. Max FRR -/60/60.
System ID FC825
Copper pipe (up to 150mm) through a 1 x 13mm plasterboard wall or concrete wall (116mm or greater). AGNI-Shield extending 150-450mm from each side of wall with AGNI-Seal sealant. Max FRR -/60/60.
System ID FC826
Steel pipe (50mm) through a 1 x 13mm plasterboard wall or concrete wall (116mm or greater). AGNI-Shield extending 150mm from each side of wall with AGNI-Seal sealant. Max FRR -/60/60.
System ID FC866
Steel pipe (42mm) through a 1 x 13mm plasterboard wall or concrete wall (116mm or greater). Double layer AGNI-Shield extending 50mm from each side of wall with AGNI-Seal sealant. Max FRR -/60/60.
System ID FC840
Steel pipe (50mm) through a 100mm CLT wall. AGNI-Shield extending 100mm from each side of wall with AGNI-Seal sealant. Max FRR -/60/60.
System ID FC235
Plastic pipe (up to 100mm) through a concrete wall. CSD Rise Ultra Wrap fitted tightly around pipe to 1/8 of diam of pipe. CSD Nofirno Sealant 5mm each side of wall for smoke and water seal.
System ID FC236
Plastic pipe (up to 100mm) through a plasterboard wall. CSD Rise Ultra Wrap fitted tightly around pipe. CSD Nofirno Sealant 5mm each side of wall for smoke and water seal. Max aperture 400x450mm.
System ID FC238
Cables, cable trays and conduit through a plasterboard or concrete wall. CSD Actifoam sheets with strips separating cables. Finish with 10mm of CSD Nofirno sealant for smoke and water tightness.
System ID FC239
Metallic pipe (up to 550mm) through a plasterboard or concrete wall. CSD Actifoam sheets and strips with 5mm CSD Nofirno sealant for smoke and water tightness.
System ID FC240
Cables (single or multiple up to 100mm) or conduit through a concrete or plasterboard wall. CSD Rise Rapid insert sleeves around each cable to ensure separation. Fill all spaces with CSD Rise Rapid or Nofirno filler sleeves. Finish with 20mm CSD Nofirno Sealant both sides of wall.
System ID FC241
Metal pipes (single or multiple) through a plasterboard or concrete wall. Pipes may be angled. CSD Nofirno filler sleeves with CSD Nofirno sealant 20mm each side of wall.
System ID FC242
Cables or cable tray through oversized aperture in plasterboard or concrete wall. CSD Actifoam or CSD Rise sleeves installed around cables/cable tray with CSD Nofirno Board to complete. CSD Nofirno fire sealant to finish. Aperture up to 1800x100mm or equivalent.
System ID FC528
PVC, PE or PP plastic pipe up to 165mm through a plasterboard or concrete wall 100mm or greater. Single or double Mulcol Multicollar Slim each side with Mulcol Sealant 10mm deep. Max FFR -/120/120
System ID FC251
Insulated PVC, PE or PP plastic pipe up to 110mm through a plasterboard or concrete wall 100mm or greater. Insulation interrupted through the wall and may be combustible or non-combustible. Single or double Mulcol Multicollar Slim each side with Mulcol Sealant 10mm deep. Max FFR -/120/120
System ID FC143
Insulated PVC, PE or PP plastic pipe up to 110mm through a plasterboard or concrete wall 100mm or greater. Insulation sustained through wall and may be combustible or non-combustible. Single or double Mulcol Multicollar Slim each side with Mulcol Sealant 10mm deep. Max FFR -/120/90
System ID FC530
PVC, PE or PP plastic pipe up to 110mm at an angle up to 45O through a plasterboard or concrete wall 100mm or greater. Closed systems only. Double Mulcol Multicollar Slim each side with Mulcol Sealant 10mm deep. Max FFR -/120/120
System ID FC478
PVC or PP plastic pipe up to 125mm with elbow through a plasterboard or concrete wall 100mm or greater. Mulcol Multicollar Slim each side with Mulcol Sealant 10mm deep. Max FFR -/90/90
System ID FC803
PVC, PE or PP plastic pipe up to 110mm with elbow through a plasterboard or concrete wall 100mm or greater with no clearance from wall. Mulcol Multicollar Slim standard fitting one side and U-shaped fitting on elbow side. Mulcol Sealant 10mm deep both sides. Max FFR -/120/120
System ID FC228
C-Purlin (200mm to 400mm) through a 1 x 13mm plasterboard wall. Tech Coatings FBL-100 Intumescent Paint applied for 300mm on fire side only (or both sides for two-way application). May be used for any rolled steel profile 1.15mm to 3mm thick. FRR -/60/60
System ID FC290
Timber trusses (with or without exposed vertical web) or purlins through a 1 x 13mm plasterboard wall. Tech Coatings FBL-100 Intumescent Paint applied for 300mm on fire side only (or both sides for two-way application). May be used for any timber 90mm x 45mm or greater. FRR -/60/60
System ID FC289
Timber trusses (with or without exposed vertical web) or purlins through a 1 x 13mm standard plasterboard wall. Tech Coatings FBL-100 Intumescent Paint applied for 300mm on fire side only (or both sides for two-way application). May be used for any timber 90mm x 45mm or greater. FRR -/30/30
System ID FC739
Service Penetration: Ventilated cavity barrier up to 25mm and 50mmSubstrate: Concrete, AAC, block, brick, timber, or existing mineral fibre insulationMax FRR: -/120/120
System ID FC904