System Selector

The System Selector below will help you choose the correct system. Simply tick the boxes that apply to your situation.
If you want to restrict your search to a particular product, click your choice from the "Product" dropdown menu. 
If you know the identification number of the system you want then simply type it in to the "System ID" box and click Search.
For an alphabetical list, click here for a list of systems.
Important Note: Systems tested in plasterboard may also be used in concrete (AS 1530.4 Section 10.12.2). Therefore all the systems shown below with diagrams in plasterboard may be used in concrete.

Plasterboard
Concrete
Timber
Wall
Floor
Ceiling
Plastic Pipe
PEX Pipe
Metal Pipe
Copper/Brass Pipe
Cables
Cable Trays
Conduits
Pair Coils
Elect Dist Box
Joints and Gaps
Combos
Ducts
Smoke Seal
Blanks
Hatches

Product :
Required Fire Rating :
System ID :

View

3M CP 25WB+ Concrete Floor Cables

System ID FC216

Cables (multiple, with or without cable tray) through a concrete floor (120mm min). 3M CP 25WB+ sealant 40mm deep at top of floor only, backed by 80mm mineral wool. Annular space 25-60mm. Thermal up to 120 available using 3M E-5A-4 Endothermic Mat.

View

3M CP 25WB+ P'board Wall Cables

System ID FC217

Cables (D1 and D2 cables as per AS1530.4, including cable trays) through a plasterboard or concrete wall. 3M CP 25WB+ sealant to 20mm to both sides of the wall, with 75mm mineral wool backing. Thermal of 120 available using 3M E-5A-4 Endothermic Mat.

View

3M CP 25WB+ P'board Wall Metal Pipes

System ID FC350

Steel, copper or ferrous pipes (uninsulated) through a plasterboard wall. 3M CP 25WB+ sealant to 25mm to both sides of wall with 100mm mineral wool backing. Thermal of 120 available using 3M E-5A-4 Endothermic Mat.

View

3M CP 25WB+ Concrete Wall Metal Pipes

System ID FC293

Steel, copper or ferrous pipes through a concrete wall. 3M CP 25WB+ sealant to 25mm to both sides of wall with 100mm mineral wool backing. Thermal of 120 available using 3M E-5A-4 Endothermic Mat.

View

3M CS-195 23695 Floor

System ID FC224

Cables D1and D2, cable trays, metallic pipes in any combination or blanks through a concrete floor min 100mm slab depth. Max aperture 425x300mm. 3M Composite Sheet CS-195, 1 or 2 layers. Wrap strips, putty and sealant as required - see detailed instructions. Insulation up to 120 by wrapping with E-5A-4 Mat

View

3M CS-195 23695 Wall

System ID FC225

Cables D1 and D2, cable trays, blanks or metallic pipes through a plasterboard or concrete wall in various combinations. Wall min 120mm thick. Aperture max 800x600mm. 3M Composite Sheet CS-195 to each side of wall. Wraps and sealant as required. Insulation increased to 120 by wrapping with E-5A-4 Mat.

View

3M IC 15WB+ 3219 P'board Wall

System ID FC292

Cables (single, multiple, with or without cable tray) and copper, ferrous or steel pipes through a plasterboard wall. 3M IC 15 WB+ sealant to 20mm (cables) or 25mm (pipes) to both sides of wall. Thermal of 120 available using 3M Fire Barrier Duct Wrap 615+.